TFP-121x Series Analogue Addressable Fire Alarm Control Panels
TFP-121X INSTALLATION AND OPERATION MANUAL
32
7.9.6.4
Loop Panel Parameter
It is used to create clearer expressions in the alarm, errors and warnings window. The expression to be written on
the screen when a loop-related condition occurs is the label defined in this very parameter.
7.10
TdNET Functions
TdNET
is a multi-master protocol and communication technology that works with Token-Passing topology that
provides the network infrastructure of Teknim addressable fire detection systems. A network is created with up to 16
devices supporting the TdNET protocol. In order to connect the TFP-121x panels to the network line, the
TFC-1208
TdNET Network Card
must be integrated through the P2 port on the motherboard.
For more information about TdNET, refer to the TFC-1208 TdNET Network Card Operating Instructions Manual.
7.10.1
TdNET Map
It lists the control panels which the panel requires to see on the network. If a panel previously added to the network
is no longer detected, it will be displayed as "Panel N/A" (Not Available) on the error screen.
TdNET list is displayed on the screen when the TdNET Map is accessed, and a panel is selected from such list and
addition to and deletion from the network memory with either "ACTIVE" or "PASSIVE" option, of the selected panel
can be achieved.
In order to add a panel to the map, follow the instructions provided below:
1
Go to
“
Menu
»
Programming
» TdNET
Functions
» TdNET
Map
”
menu,
2
Select the panel required to be added using Up and Down keys,
3
Press
“OK”
key and change the form value to the
“A
CTIVE
”
,
4
Press
“OK”
and thereafter
“ESC”
key in order to save and complete the process.
Figure 30 - TdNET Map, Only Panel 2, 3 and 4 are being monitored
7.10.2
TdNET Parameters
The general settings of the panel for TdNET are made with the TdNET parameters menu. All parameters included in
this menu are reviewed in detail below.
1
TdNET Mode
a.
Independent : Default value. The panel will not send any messages to the network line. It does not
evaluate any messages coming through the network. However, it continues to listen to the devices
available on the network.
b.
Station
: evaluates all error, alarming, warning information coming from any zone located on the
network. Every panel selected as a station continually communicates error, alarming, warning
information to the network line without making any adjustments.
c.
Main Panel : is same as the station mode. It also sends time synchronization, night/day mode, delay
active /the passive commands to network line. There should be only one main panel on the network
line.