Adjust Menus
363
Adjust
Menu (4 of 5)
•
•
C4
•
•
•
•
B1
B1
C1
C1
•
•
•
C1
•
•
•
C1
•
•
•
•
C1
•
•
C2
B1
•
•
•
•
The time delay the control can expect between the
time the boiler contact closes and the burner fires.
The thermal mass characteristics of the boiler that
is being used.
The differential that the control is to use when it is
operating the boiler.
The device that is being used to supply flow to the
heat exchanger in the DHW storage tank.
No Indirect DHW tank =
NONE
The DHW storage tank’s temperature during the
Occupied period.
10K 2 = DHW
DHW THRU
≠
NONE
The DHW storage tank’s temperature during the
UnOccupied period.
DIP switch =
Setback
10K 2 = DHW
DHW THRU
≠
NONE
The minimum boiler supply temperature to the
DHW storage tank during the Occupied period.
10K 2
≠
DHW
DHW THRU
≠
NONE
Selects whether or not DHW will be generated
during the UnOccupied period.
DIP switch =
Setback
10K 2
≠
DHW
DHW THRU
≠
NONE
The portions of the heating system that the DHW
will have priority over.
DHW THRU
≠
NONE
The minimum boiler supply temperature when a
setpoint demand is present during the Occupied
period.
10K 2 = DHW,
OR
DHW THRU = NONE
0:00 to 3:00
min
(1 sec. increments)
Default =
0:10 min
LITE, MED, HEVY
Default =
MED
AUTO, 2 to 42˚F
(1 to 23˚C)
Default =
AUTO
NONE, PUMP, VALV
Default =
PUMP
OFF, 70 to 190˚F
(OFF, 21 to 88˚C)
Default =
140
°
F (60
°
C)
OFF, 70 to 190˚F
(OFF, 21 to 88˚C)
Default =
120
°
F (49
°
C)
OFF, 100 to 220˚F
(OFF, 38 to 104˚C)
Default =
180
°
F (83
°
C)
OFF, DHW XCHG
Occ
Default =
OFF
NONE, MIX, B+M
(Mixing)
Default =
NONE
OFF, 70 to 220˚F
(OFF, 21 to 104˚C)
Default =
180
°
F (82
°
C)
Occ
UnOcc
Occ
UnOcc
Occ
Actual
Setting
Section
LT
D
INST
ADV
Range
Access
Level
Description
Item Field