26 of 40
Copyright © D 363 -06/99
363
Adjust
Menu (3 of 5)
Occ
UnOcc
35 to 100˚F
(2 to 38˚C)
Default =
70
°
F (21
°
C)
The desired room air temperature during an
Occupied period for the boiler zone(s).
Note: There
is only a
±
3
°
F adjustment in the LTD access level.
DIP switch =
Characterized Heating Curve
35 to 100˚F
(2 to 38˚C)
Default =
65
°
F (18
°
C)
OFF, 0:20 to 8:00 Hr.
Default =
OFF
0 to 50˚F
(0 to 28˚C)
Default =
15
°
F (8
°
C)
The desired room air temperature during an
UnOccupied period for boiler zone(s).
DIP switch =
Characterized Heating Curve
DIP switch =
Setback
The amount of morning boost.
DIP switch =
Characterized Heating Curve
DIP switch =
Setback
10K 1
≠
Boil
The amount that the boiler supply temperature
will be reduced when the control is in an
UnOccupied mode.
DIP switch =
Reset Ratio
DIP switch =
Setback
The type of terminal units that are being used for
the boiler side of the system.
DIP switch =
Characterized Heating Curve
The design indoor air temperature used in the
heat loss calculation for the boiler system.
DIP switch =
Characterized Heating Curve
The starting water temperature used in the reset
ratio calculation for the boiler supply.
DIP switch =
Reset Ratio
The design supply temperature used in the heat
loss calculation for the boiler system.
The maximum temperature allowed for the boiler
target temperature.
The minimum temperature allowed for the boiler
target temperature.
35 to 100˚F
(2 to 38˚C)
Default =
70
°
F (21
°
C)
35 to 150˚F
(2 to 66˚C)
Default =
70
°
F (21
°
C)
70 to 220˚F
(21 to 104˚C)
Default =
190
°
F (88
°
C)
120 to 225˚F, OFF
(49 to 107˚C, OFF)
Default =
210
°
F (99
°
C)
OFF, 80 to 180˚F
(OFF, 27 to 82˚C)
Default =
140
°
F (60
°
C)
•
•
B1
•
•
•
•
•
•
•
B1
A
B1
A
•
•
B1
•
•
B1
•
•
•
•
B1
•
B1
B1
•
•
•
•
•
HRF1
(Heavy),
HRF2
(Light), (Fan-)
COIL
,
CONV
(ector),
RAD
(iator),
BASE
(board)
Default =
CONV
Section
LT
D
INST
ADV
Range
Access
Level
Description
Item Field
USER
Adjust Menus