Troubleshooting
The number of times that a communication error has been detected
between the control and either an RTU or RDM since this item
was last cleared. If the wires between the control and either the
RTU or RDM are run in a noisy electrical environment, this can
cause interference in the communication between the control and
the RTU or RDM.
363
Monitor
Menu (3 of 3)
0 - 255
0 - 255
0 - 255
The number of times that the microprocessor in the control has
had to reset itself since this item was last cleared. The control will
reset itself if it has experienced some form of interference that
has disrupted its operation. This can be used to give an indication
of the quality of the electrical environment that the control has
been installed in.
The number of times the control has been powered up since this
item was last cleared. This number will increase if there is a lowering
of the input voltage beyond the control’s usable range. This item
can be used as an indication of the quality of the power source.
•
•
•
USER
LT
D
INST
ADV
Range
Access
Level
Description
Item Field
Note:
To clear the recorded information in the specific Item field, press and hold and .
Error Displayed
Description of Error
363
Error
Messages (1 of 4)
The control was unable to store a piece of information into its EEPROM. This error can be caused by
a noisy power source. The control will display the error message and will continue to operate as normal.
Pressing either the Menu or Item button will clear this error.
The control was unable to read a piece of information stored in the Adjust menu. Because of this, the
control was required to load the factory settings into all of the items in the Adjust menu. The control
will stop operation until all of the items available in the Adjust menu of the control have been checked
by the user or installer.
Note: Access level must be
ADV
in order to clear the error.
The control was unable to read a piece of information stored in the Monitor menu. Because of this,
the control was required to load the factory settings into all of the items in the Monitor menu. The
control will continue to display the error message until all of the items available in the Monitor menu
of the control have been checked by the user or installer.
Note: Access level must be
ADV
in order to
clear the error.
The control was unable to read a piece of information stored in the Miscellaneous menu. Because of
this, the control was required to load the factory settings into all of the items in the Miscellaneous
menu. The control will continue to display the error message until all of the items available in the
Miscellaneous menu of the control have been checked by the user or installer.
Note: Access level must
be
ADV
in order to clear the error.
The control was unable to read a piece of information from the A/D system. This is the system that
the control uses to read the sensor inputs. If this error occurs, it is an indication that the sensor wires
have been run in a noisy electrical environment. To clear this error, press either the Menu or Item
buttons. The control will stop operation until the A/D fault is corrected.
The RTU was unable to store a piece of information to the EEPROM. This error can be caused by a
noisy power source to the control. The control will display the error message and will continue to
operate as normal. Pressing either the Menu or Item button will clear this error.
The control was unable to read a piece of information stored in the Schedule menu. Because of this,
the control was required to load the factory settings into all of the items in the Schedule menu. The
control will continue to display the error message until all of the items available in the Schedule menu
of the control have been checked by the user or installer.
Note: Access level must be
ADV
in order to
clear the error.