BOILER MASS

The boiler mass setting allows the installer to adjust the control to the thermal mass of the type of heat sources used in the 
application. There is a boiler mass setting for each boiler. The modulation of the boiler can become unstable if the incorrect Boiler 
Mass setting is chosen. A key sign of the boiler modulation being unstable is the flame will continue to increase and then decrease 
in short periods of time. By choosing a lower boiler mass setting, the boiler response will become more stable. 

Lo (1)

The Lo setting is selected if the boiler that is used has a low thermal mass. This means that the boiler has a very small water 
content and has very little metal in the heat exchanger. A boiler that has a low thermal mass comes up to temperature quite 
rapidly when fired. This is typical of many copper fin-tube boilers.

The Lo mass setting provides a fast response to the heating system.

number into the Maximum Boiler Output setting.

For example, if a boiler has a maximum output of 100 MBH:

Maximum Boiler Output = 100,000 BTU/hr = 10 x 10,000 BTU/hr

 10,000

MOTOR SPEED

The Motor Speed is the amount of time the boiler requires to go from 0% 
modulation to 100% modulation. The control includes a Motor Speed 
setting for each individual boiler.

Gas valve actuating motors have a design time from fully closed to fully 
opened which can be found in the manufacturer’s manual. The Motor 
Speed should be set to this time.

The Motor Speed setting for a Variable Frequency Drive (VFD) is the 
amount of time required to go from a stopped position to 100% fan 
speed. Since a VFD has a very quick response rate, it may be necessary 
to increase the Motor Speed setting in order to increase the stability of 
the boiler modulation.

Example 1:

A boiler’s input signal range is 2 to 9 V (dc). The 265 control has an output signal range of 2 to 10 V (dc). To make the two signal 
ranges the same, the Maximum Modulation required is:

Maximum Modulation = 2 V – 9 V  x 100% = 88%

 

2 V – 10 V

Example 2:  

If the boiler’s input signal range is 6 to 19 mA the required Maximum Modulation is:

Maximum Modulation = 4 mA – 19 mA  x 100% = 94%

 

4 mA – 20 mA

MINIMUM BOILER OUTPUT

In order to accommodate different boiler capacities in the same system, a minimum boiler output for each boiler can be set. This 
allows the control to properly operate the boilers using either sequential or parallel modulation. The minimum boiler output range 
is from 10,000 BTU / hour to 19,990,000 BTU / hour.

Each boiler typically has a rating plate that specifies the minimum output. This information is also available in the boiler manual. The 
Minimum Boiler Output setting has units of 10,000 BTU / hour. Divide the minimum output rating by 10,000 and enter the number 
as the Minimum Boiler Output setting.

For example, if a boiler has a minimum output of 20 MBH:

Minimum Boiler Output = 20,000 BTU/hr = 2 x 10,000 BTU/hr

 10,000

MAXIMUM BOILER OUTPUT

In order to accommodate different boiler capacities in the same system, there is a maximum boiler output for each boiler. This 
allows the control to properly operate the boilers using either sequential or parallel modulation. The maximum boiler output range 
is from 10,000 BTU / hour to 19,990,000 BTU / hour.

Each boiler typically has a rating plate that specifies the maximum output. This information is also available in the boiler manual. 
The Maximum Boiler Output setting has units of 10,000 BTU / hour. Divide the maximum output rating by 10,000 and enter the 

Summary of Contents for Boiler Control 265

Page 1: ...dulating Boiler Output Boiler Enable Output Pump Output Boiler Enable or Pump Input Setpoint or DHW Demand Input 115 V ac Power Supply Output Primary Pump Input Timer or Switch Optional Output Combust...

Page 2: ...he 265 has four push buttons Menu Item for selecting and adjusting settings As you program your control record your settings in the ADJUST Menu table which is found in the second half of this brochure...

Page 3: ...ontrol is in UnOccupied Mode Primary Pump Displays when the primary pump relay is turned on Occupied Schedule Displays when the control is in Occupied Mode Boiler Pump Displays which boiler pump relay...

Page 4: ...ply water temperature to a hydronic space heating system or setpoint When using the control to provide Domestic Hot Water DHW requirements only two modulating boilers can be operated The supply water...

Page 5: ...t setting This alert can be used to determine if the boilers have failed to fire To reset the alert press and hold the and buttons for 5 seconds while in the VIEW menu ROTATION The control includes an...

Page 6: ...ATION Boiler 1 Boiler 2 Boiler 3 100 MOD OFF PARALLEL MODULATION Boiler 1 Boiler 2 Boiler 3 MOD MOD MOD SEQUENTIAL MODULATION The control offers a sequential modulation option This is selected by sett...

Page 7: ...culate the Maximum Modulation use the following formulae For 4 to 20 mA Maximum Modulation 4 mA Boiler s Maximum Input Signal x 100 4 20 mA For 0 to 10 V dc Maximum Modulation 0 V dc Boiler s Maximum...

Page 8: ...onse rate it may be necessary to increase the Motor Speed setting in order to increase the stability of the boiler modulation Example 1 A boiler s input signal range is 2 to 9 V dc The 265 control has...

Page 9: ...ve PID logic in order to satisfy the boiler target temperature Fixed Differential If the user desires to have a fixed differential this is set using the boiler differential setting in the ADJUST menu...

Page 10: ...to thermally shock a boiler when it is shut off at high fire The Soft Stop feature forces the boiler to modulate down to minimum before turning off This is designed to prevent large volumes of cold ai...

Page 11: ...49 C 140 F 60 C 190 F 88 C 180 F 82 C 160 F 71 C 150 F 66 C BOIL MAX 140 F 60 C 160 F 71 C 210 F 99 C 200 F 93 C 180 F 82 C 170 F 77 C BOIL MIN OFF OFF 140 F 60 C 140 F 60 C 140 F 60 C 140 F 60 C High...

Page 12: ...nter in the display When the control is in WWSD the Boiler Demand pointer is displayed if there is a boiler demand However the control does not operate the heating system to satisfy this demand The co...

Page 13: ...HG The DHW demand overrides the boiler reset target temperature except when the boiler reset target is higher than the DHW Exchange setting DHW MODE AND PRIORITY OPERATION The control has five differe...

Page 14: ...nues this purge for a maximum of two minutes or until the boiler supply water temperature drops 20 F 11 C below the boiler target temperature during the DHW operation The control also stops the purge...

Page 15: ...the boiler supply temperature is sufficiently reduced the Boiler 3 DHW contact shuts off The heating system is turned on for a period of time to prevent the building from cooling off After a period o...

Page 16: ...iler SETP MODE 2 Setpoint in Parallel with Priority Whenever a setpoint demand is present the boiler s is operated to maintain the setpoint target and the primary pump Prim P1 contact is opened It is...

Page 17: ...mary pump and boiler pumps operate as described in section G INPUT SIGNAL The control can accept either a 0 10 V dc signal or a 2 10 V dc signal The External Input Signal setting must be set to the pr...

Page 18: ...Pump Boiler Pumps Primary Pump Boiler Pumps Primary Pump Boiler Pumps OR Example Range 0 10 V dc Input 7 V dc 157 F 69 C Offset 5 F 3 C 5 F 3 C Boiler Target 162 F 72 C CONVERSION TABLE 0 10 0 20 mA 0...

Page 19: ...g to cross between sections as the wires will interfere with safety dividers which should be installed at a later time Power must not be applied to any of the wires during the rough in wiring stage Al...

Page 20: ...DHW MODE must also be set to 1 through 4 Setpoint Demand To generate a Setpoint Demand a voltage between 24 V ac and 230 V ac must be applied across the Setp DHW Dem and Com Dem terminals 31 and 30 T...

Page 21: ...There is no power available on these terminals from the control These terminals are to be used as a switch to enable the modulating boiler Since this is an isolated contact it may switch a voltage be...

Page 22: ...to 0 to 10 V dc using an external 500 resistor across the Mod 1 Mod 2 Mod 3 terminals The 4 to 20 mA output can be converted to a 0 135 output for a Modutrol IV gas valve actuating motor using a 0 135...

Page 23: ...the control to measure the boiler supply water temperature Boiler Return Sensor Connect the two wires from the Boiler Return Sensor 071 to the Com and Boil terminals 1 and 3 The boiler return sensor i...

Page 24: ...3 and 14 using an AC voltmeter the reading should be between 103 5 and 126 5 V ac Test the Powered Inputs Boiler Demand If a boiler demand is used measure the voltage between the Boil Dem and Com Dem...

Page 25: ...2 are running If the boiler s operates properly disconnect the power and remove the jumper Boiler 3 DHW Contact Boiler Operation If a boiler is connected to the Boiler 3 DHW contact 21 and 22 make sur...

Page 26: ...switch settings change the items that are available to be viewed and or adjusted in the User Interface If a DIP switch is changed while the control is powered up the control responds to the change in...

Page 27: ...h is set to Exercise the pumps are operated for 10 seconds after every three days of inactivity Parallel Sequential The Parallel Sequential DIP switch selects whether to modulate the boilers using par...

Page 28: ...0 Boiler 2 Modulation Current percent modulation of the boiler s burner This item is only available when Boiler 2 is set to Au automatic or CP1 copy 1 0 to 100 Boiler 3 Modulation Current percent modu...

Page 29: ...Default Au B Boiler 2 Selects whether or not boiler 2 is operational CP1 copies the settings of Boiler 1 to Boiler 2 CP1 Au Auto OFF Default CP1 B Boiler 3 Selects whether or not boiler 3 is operation...

Page 30: ...iler and when the burner actually fires This item is only available when Boiler 1 is set to Au automatic 0 00 to 4 00 minutes 1 sec increment Default 0 10 min B Boiler Mass 1 The thermal mass characte...

Page 31: ...hour This item is only available when Boiler 2 is set to Au automatic or CP1 copy 1 1 to 1999 Default 10 B Maximum Boiler 2 Output The maximum boiler 2 output in 10 000 s of BTU hour This item is onl...

Page 32: ...t to Au automatic or CP1 copy 1 and DHW MODE is set to OFF 0 to 50 Default 0 B Maximum Modulation 3 The maximum percent modu lation of the burner This item is only available when Boiler 3 is set to Au...

Page 33: ...C WWSD Occupied The system s warm weather shut down temperature during the Occupied period This item is only available when the External Input Stand Alone DIP switch is set to Stand Alone 35 to 100 F...

Page 34: ...If Boiler 3 is set to OFF and DHW MODE is set to 3 or 4 the DHW contact is closed and the primary pump stays on If Boiler 3 is set to OFF and DHW MODE is set to 1 or 2 the DHW contact is closed and th...

Page 35: ...it The control will not operate the boiler s until the sensor is repaired Locate and repair the problem as described in the Data Brochure D 070 To clear the error message from the control after the se...

Page 36: ...HEALTH OR SAFETY LEGISLATION THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY FOUR 24 MONTHS FROM THE PRODUCTION DATE TO THE EXT...

Reviews: