background image

© 

2010     D 

265 

07/10 

of 

36 

How To Use The Data Brochure

User Interface

Table of Contents

Installation .......................................................Pg  19

DIP Switch Settings ........................................Pg 26

Control Settings ..............................................Pg 28

 

View Menu

 ..............................................Pg 28

 
 

Adjust Menu

 ...........................................Pg 29

 
Testing the Control .........................................Pg 34

Error Messages ...............................................Pg 35

Technical Data .................................................Pg 36

Limited Warranty ............................................Pg 36

User Interface ..................................................Pg 2

Display .............................................................Pg  3

Sequence of Operation ..................................Pg 4

 
 

Section A: General Operation

 ..............Pg 4

 
 

Section B: Boiler Operation

..................Pg 6

 
 

Section C: Outdoor Reset

 .....................Pg  10

 
 

Section D: DHW Operation

 ...................Pg 13

 
 

Section E: Setpoint Operation

 .............Pg 16

 
 

Section F: External Input Operation

 ....Pg  17

 
 

Section G: Pump Operation

 ..................Pg 18

This  brochure  is  organized  into  four  main  sections.  They  are:  1)  Sequence  of  Operation,  2)  Installation,  3)  Control  Settings,  and 
4) Testing and Troubleshooting. The Sequence of Operation section has seven sub-sections. We recommend reading Section A: 
General of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the 
sub sections that apply to your installation.

The Control Settings section (starting at DIP Switch Settings) of this brochure describes the various items that are adjusted and 
displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.

The 265 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to setup and monitor 
the operation of your system. The 265 has four push buttons (

Menu, Item,

 

) for selecting and adjusting settings. As you 

program your control, record your settings in the ADJUST Menu table which is found in the second half of this brochure.

Menu

All of the items displayed by the control are organized into various menus. These menus 
are listed on the left hand side of the display (Menu Field). To select a 

menu

, use the 

Menu 

button. By pressing and releasing the 

Menu 

button, the display will advance to 

the next available menu. Once a menu is selected, there will be a group of items that can 
be viewed within the menu.

Item

The abbreviated name of the selected item will be displayed in the item field of the 
display. To view the next available item, press and release the 

Item

 button. Once you 

have reached the last available item in a menu, pressing and releasing the 

Item

 button 

will return the display to the first item in the selected menu.

The items can be quickly scrolled through by holding the 

Item

 button and then pressing 

the 

 button. To rapidly scroll through the items in the reverse order, hold the 

Item

 button 

and press the 

 button.

Adjust

To make an adjustment to a setting in the control, begin by selecting the appropriate 
menu using the 

Menu 

button. Then select the desired item using the 

Item 

button. Finally, 

use the 

 and / or 

 button to make the adjustment.

Additional information can be gained by observing the Status field of the LCD. The status 
field will indicate which of the control’s outputs are currently active. Most symbols in the 
status field are only visible when the VIEW Menu is selected.

Menu

Item

Menu

Item

Menu

Item

Summary of Contents for Boiler Control 265

Page 1: ...dulating Boiler Output Boiler Enable Output Pump Output Boiler Enable or Pump Input Setpoint or DHW Demand Input 115 V ac Power Supply Output Primary Pump Input Timer or Switch Optional Output Combust...

Page 2: ...he 265 has four push buttons Menu Item for selecting and adjusting settings As you program your control record your settings in the ADJUST Menu table which is found in the second half of this brochure...

Page 3: ...ontrol is in UnOccupied Mode Primary Pump Displays when the primary pump relay is turned on Occupied Schedule Displays when the control is in Occupied Mode Boiler Pump Displays which boiler pump relay...

Page 4: ...ply water temperature to a hydronic space heating system or setpoint When using the control to provide Domestic Hot Water DHW requirements only two modulating boilers can be operated The supply water...

Page 5: ...t setting This alert can be used to determine if the boilers have failed to fire To reset the alert press and hold the and buttons for 5 seconds while in the VIEW menu ROTATION The control includes an...

Page 6: ...ATION Boiler 1 Boiler 2 Boiler 3 100 MOD OFF PARALLEL MODULATION Boiler 1 Boiler 2 Boiler 3 MOD MOD MOD SEQUENTIAL MODULATION The control offers a sequential modulation option This is selected by sett...

Page 7: ...culate the Maximum Modulation use the following formulae For 4 to 20 mA Maximum Modulation 4 mA Boiler s Maximum Input Signal x 100 4 20 mA For 0 to 10 V dc Maximum Modulation 0 V dc Boiler s Maximum...

Page 8: ...onse rate it may be necessary to increase the Motor Speed setting in order to increase the stability of the boiler modulation Example 1 A boiler s input signal range is 2 to 9 V dc The 265 control has...

Page 9: ...ve PID logic in order to satisfy the boiler target temperature Fixed Differential If the user desires to have a fixed differential this is set using the boiler differential setting in the ADJUST menu...

Page 10: ...to thermally shock a boiler when it is shut off at high fire The Soft Stop feature forces the boiler to modulate down to minimum before turning off This is designed to prevent large volumes of cold ai...

Page 11: ...49 C 140 F 60 C 190 F 88 C 180 F 82 C 160 F 71 C 150 F 66 C BOIL MAX 140 F 60 C 160 F 71 C 210 F 99 C 200 F 93 C 180 F 82 C 170 F 77 C BOIL MIN OFF OFF 140 F 60 C 140 F 60 C 140 F 60 C 140 F 60 C High...

Page 12: ...nter in the display When the control is in WWSD the Boiler Demand pointer is displayed if there is a boiler demand However the control does not operate the heating system to satisfy this demand The co...

Page 13: ...HG The DHW demand overrides the boiler reset target temperature except when the boiler reset target is higher than the DHW Exchange setting DHW MODE AND PRIORITY OPERATION The control has five differe...

Page 14: ...nues this purge for a maximum of two minutes or until the boiler supply water temperature drops 20 F 11 C below the boiler target temperature during the DHW operation The control also stops the purge...

Page 15: ...the boiler supply temperature is sufficiently reduced the Boiler 3 DHW contact shuts off The heating system is turned on for a period of time to prevent the building from cooling off After a period o...

Page 16: ...iler SETP MODE 2 Setpoint in Parallel with Priority Whenever a setpoint demand is present the boiler s is operated to maintain the setpoint target and the primary pump Prim P1 contact is opened It is...

Page 17: ...mary pump and boiler pumps operate as described in section G INPUT SIGNAL The control can accept either a 0 10 V dc signal or a 2 10 V dc signal The External Input Signal setting must be set to the pr...

Page 18: ...Pump Boiler Pumps Primary Pump Boiler Pumps Primary Pump Boiler Pumps OR Example Range 0 10 V dc Input 7 V dc 157 F 69 C Offset 5 F 3 C 5 F 3 C Boiler Target 162 F 72 C CONVERSION TABLE 0 10 0 20 mA 0...

Page 19: ...g to cross between sections as the wires will interfere with safety dividers which should be installed at a later time Power must not be applied to any of the wires during the rough in wiring stage Al...

Page 20: ...DHW MODE must also be set to 1 through 4 Setpoint Demand To generate a Setpoint Demand a voltage between 24 V ac and 230 V ac must be applied across the Setp DHW Dem and Com Dem terminals 31 and 30 T...

Page 21: ...There is no power available on these terminals from the control These terminals are to be used as a switch to enable the modulating boiler Since this is an isolated contact it may switch a voltage be...

Page 22: ...to 0 to 10 V dc using an external 500 resistor across the Mod 1 Mod 2 Mod 3 terminals The 4 to 20 mA output can be converted to a 0 135 output for a Modutrol IV gas valve actuating motor using a 0 135...

Page 23: ...the control to measure the boiler supply water temperature Boiler Return Sensor Connect the two wires from the Boiler Return Sensor 071 to the Com and Boil terminals 1 and 3 The boiler return sensor i...

Page 24: ...3 and 14 using an AC voltmeter the reading should be between 103 5 and 126 5 V ac Test the Powered Inputs Boiler Demand If a boiler demand is used measure the voltage between the Boil Dem and Com Dem...

Page 25: ...2 are running If the boiler s operates properly disconnect the power and remove the jumper Boiler 3 DHW Contact Boiler Operation If a boiler is connected to the Boiler 3 DHW contact 21 and 22 make sur...

Page 26: ...switch settings change the items that are available to be viewed and or adjusted in the User Interface If a DIP switch is changed while the control is powered up the control responds to the change in...

Page 27: ...h is set to Exercise the pumps are operated for 10 seconds after every three days of inactivity Parallel Sequential The Parallel Sequential DIP switch selects whether to modulate the boilers using par...

Page 28: ...0 Boiler 2 Modulation Current percent modulation of the boiler s burner This item is only available when Boiler 2 is set to Au automatic or CP1 copy 1 0 to 100 Boiler 3 Modulation Current percent modu...

Page 29: ...Default Au B Boiler 2 Selects whether or not boiler 2 is operational CP1 copies the settings of Boiler 1 to Boiler 2 CP1 Au Auto OFF Default CP1 B Boiler 3 Selects whether or not boiler 3 is operation...

Page 30: ...iler and when the burner actually fires This item is only available when Boiler 1 is set to Au automatic 0 00 to 4 00 minutes 1 sec increment Default 0 10 min B Boiler Mass 1 The thermal mass characte...

Page 31: ...hour This item is only available when Boiler 2 is set to Au automatic or CP1 copy 1 1 to 1999 Default 10 B Maximum Boiler 2 Output The maximum boiler 2 output in 10 000 s of BTU hour This item is onl...

Page 32: ...t to Au automatic or CP1 copy 1 and DHW MODE is set to OFF 0 to 50 Default 0 B Maximum Modulation 3 The maximum percent modu lation of the burner This item is only available when Boiler 3 is set to Au...

Page 33: ...C WWSD Occupied The system s warm weather shut down temperature during the Occupied period This item is only available when the External Input Stand Alone DIP switch is set to Stand Alone 35 to 100 F...

Page 34: ...If Boiler 3 is set to OFF and DHW MODE is set to 3 or 4 the DHW contact is closed and the primary pump stays on If Boiler 3 is set to OFF and DHW MODE is set to 1 or 2 the DHW contact is closed and th...

Page 35: ...it The control will not operate the boiler s until the sensor is repaired Locate and repair the problem as described in the Data Brochure D 070 To clear the error message from the control after the se...

Page 36: ...HEALTH OR SAFETY LEGISLATION THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY FOUR 24 MONTHS FROM THE PRODUCTION DATE TO THE EXT...

Reviews: