Adjust
Menu (1 of 5)
C
Room Occupied
The desired room air temperature
during the occupied period.
This item is only available when the
External Input
/
Stand
Alone DIP switch
is set to Stand Alone.
35 to 100°F
(2 to 38°C)
Default = 70°F (21°C)
C
Room Unoccupied
The desired room air temperature
during the UnOccupied period.
This item is only available when the
External Input
/
Stand
Alone DIP switch
is set to Stand Alone.
35 to 100°F
(2 to 38°C)
Default = 65°F (18°C)
F
External Input Signal
Selects the range of the external
input signal.
This item is only available when the
External Input
/
Stand
Alone DIP switch
to External Input.
0:10, 2:10
Default = 0:10
F
Offset
Sets the temperature offset used in calculat-
ing the boiler target temperature with an external input
signal.
This item is only available when the
External Input
/
Stand
Alone DIP switch is set to
External Input.
-10 to 10°F
(-6 to 6°C)
Default = 0°F (0°C)
C
Boost
The amount of morning boost when changing
from the UnOccupied to the Occupied period.
This item is only available when the
External Input
/
Stand
Alone DIP switch
is set to Stand Alone.
OFF, 0:20 to 8:00 hr
(5 minute increment)
Default = OFF
B
Boiler 1
Selects whether or not boiler 1 is operational.
Au (Auto), OFF
Default = Au
B
Boiler 2
Selects whether or not boiler
2 is operational.
CP1 copies the settings of Boiler
1 to Boiler 2.
CP1, Au (Auto), OFF
Default = CP1
B
Boiler 3
Selects whether or not boiler
3 is operational.
This item is only available when DHW MODE is set to
OFF. CP1 copies the settings of Boiler
1 to Boiler
3.
CP1, Au (Auto), OFF
Default = CP1
C
Outdoor Design
The design outdoor air temperature used
in the heat loss calculations for the heating system.
This item is only available when the
External Input /
Stand Alone DIP switch
is set to Stand Alone.
-60 to 45°F
(-51 to 7°C)
Default = 10°F (-12°C)
C
Terminal Unit
The type of terminal units that are being
used in the heating system.
This item is only available when the
External Input /
Stand Alone DIP switch
is set to Stand Alone.
1
(HRF1),
2
(HRF2),
3
(COIL),
4
(CONV),
5
(RAD),
6
(BASE)
Default =
4
C
Boiler Indoor
The design indoor air temperature used
in the heat loss calculation for the heating system.
This item is only available when the
External Input /
Stand Alone DIP switch
is set to Stand Alone.
35 to 100°F
(2 to 38°C)
Default = 70°F (21°C)
C
Boiler Design
The design supply water temperature used
in the heat loss calculations for the heating system.
This item is only available when the
External Input /
Stand Alone DIP switch
is set to Stand Alone.
70 to 220°F
(21 to 104°C)
Default = 180°F (82°C)
Display
Description
Range
Section
Installer
Ad
v
Actual
Setting