60
4-05
Multi-
function Input
MI2 Selection
00- REV of 3 wires CTL
14- PID disable
01- Run Command by OP
15- PID (I) Reset
02- Run Command by TMN 16- OH pre-alarm
03- Fault Reset
17- External Fault (N.O.)
04- Multi-step SPD 1
18- External Fault (N.C.)
05- Multi-step SPD 2
19 & 20- Reserved
06- Multi-step SPD 3
21- SPD Search from 1-03
07- JOG Frequency REF
22- SPD Search from FRQ REF
08- ACC/ DEC Time1/ 2
switching
23- TIMER Function Input
24- MOP UP/ DN ( only for 4-
08
,
then MI4-UP/ MI5-DN)
09- ACC/ DEC disable
10- B.B. Input (N.O.)
25- Count present value clear
11- B.B. Input (N.C.)
26- Counter Input
12- FWD JOG (FJOG) Run
27~ 31- Reserved
13- REV JOG (RJOG) Run
*: The setting value of Multi-function Digital Inputs must
meet the rule of MI2< MI3< MI4< MI5.
3
4-06
Multi-
function Input
MI3 Selection
4
4-07
Multi-
function Input
MI4 Selection
5
4-08
Multi-
function Input
MI5 Selection
6
4-09
Control Terminal Signal Scan Time
0- Scan 1 Time (5ms)
1- Scan 2 Times (10ms)
1
4-10
Analog Input Filter Constant
1~ 80
10
4-11
Counter Target Value
0~ 9999
0
5- Multi-preset Reference & Auto Process Operation Parameters
No.
Parameter Name & Description
Setting Range
Default
User set
5-01
Preset Reference 1
0.0~ 400.0Hz
0.0Hz(
☆
)
5-02
Preset Reference 2
0.0~ 400.0Hz
0.0Hz(
☆
)
5-03
Preset Reference 3
0.0~ 400.0Hz
0.0Hz(
☆
)
5-04
Preset Reference 4
0.0~ 400.0Hz
0.0Hz(
☆
)
5-05
Preset Reference 5
0.0~ 400.0Hz
0.0Hz(
☆
)
5-06
Preset Reference 6
0.0~ 400.0Hz
0.0Hz(
☆
)
5-07
Preset Reference 7
0.0~ 400.0Hz
0.0Hz(
☆
)
5-08
Preset Reference 8
0.0~ 400.0Hz
0.0Hz(
☆
)
5-09
Auto Process Operation Mode Selection:
0- Auto Process is disabled.
1- Executes 1 Cycle operation then stop.
2- Continuously Executes Cycles Operation.
3- Executes 1 Cycle operation then Keep running at last Preset REF.
4- Executes 1 Cycle operation then stop.
5- Continuously Executes Cycles Operation.
6- Executes 1 Cycle operation then Keep running at last Preset REF.
*5-09= 1~ 3, if the run command is given again after F8 stopped, the F8
will start to run from the Frequency Reference before last stop.
5-09= 4~ 6, if the run command is given again after F8 stopped, the F8
will start to run from the Preset Reference 1.
0
5-10
Process Operating Mode Selection 1
0- STOP
1- FWD
2- REV
0
5-11
Process Operating Mode Selection 2
0
5-12
Process Operating Mode Selection 3
0
Summary of Contents for TDS-F8
Page 13: ...11 1 7 基本配線 圖 1 3 變頻器標準配線圖 表示主回路端子 表示控制端子 ...
Page 22: ...20 3 3 操作器操作 顯示模式說明 一體式操作器 TDS F8 變頻器內含一體式的數位操作器外 其操作方式分別說明如下 A 一體式操作器操作顯示模式 ...
Page 38: ...36 衰減特性 ...
Page 39: ...37 6 5 數位操作器安裝尺寸 TMCA V8 LED ...
Page 40: ...38 TMCA V803 LED 操作器與外拉固定框尺寸 TMCA V803 LED 外拉固定框 75 4 44 71 4 102 4 21 5 24 98 4 102 4 74 ...
Page 57: ...55 3 3 Menu Structure for Operators Local Operator LOP Fig 3 3 LOP Screen Structure ...
Page 72: ...70 6 5 Mounting Dimension of External Remote Operator TMCA V8 LED Dimension ...