4-31
RUN Command
S1
RUN
STOP
ON
OFF
ON
OFF
T
Hz
7) 03- 00~03- 04=
【
12
】
Main/ Alternative run source select.
When an input terminal is set to function
【
12
】
and is turned on, the run command source is according
to parameter 00-03(Alternative Run source).If the Input is off it will be according to 00-02 ( Main run
source).
8) 03- 00~03- 04=
【
13
】
Main/ Alternative Frequency source Select
When an input terminal is set to function
【
13
】
and is turned on, the frequency source is according to
parameter 00-06(Alternative Frequency source).If the Input is off it will be according to 00-05 ( Main
Frequency source).
9) 03- 00~03- 04=
【
14
】
Rapid Stop (controlled deceleration stop)
When an input terminal is set to function
【
14
】
and is turned on , inverter decelerates to stop.
10) 03- 00~03- 04=
【
15
】
Base Block (Coast to stop)
When an input terminal is set to function
【
15
】
and is turned on, inverter output is turned off.
11) 03- 00~03- 04=
【
16
】
Disable PID Function.
When an input terminal is set to function
【
16
】
and is turned on, PID functions is disabled, if it is turned
off , PID function is enabled again.
12) 03- 00~03- 04=
【
17
】
Reset
When a failure that can be manually reset occurs, turn on a terminal with function
【
17
】
, the failure
will be reset. (Same function as the Reset button on keypad).
13) 03- 00~03- 04=
【
18
】
Auto _ Run Mode
When an input terminal is set to function
【
18
】
, the programmable auto- sequencer function is enabled,
Refer to description of parameter group 6.
03- 06
Up/Down frequency step
Range
【
0.00~5.00
】
Hz
Example
:
S1
:
03- 00=
【
8
】
Up
frequency command, S2
:
03- 01=
【
9
】
Down
frequency command,
03- 06=
【
△
】
Hz
Mode1
:
If UP or DOWN input terminals are turned on for less than 2 seconds, for every On operation
frequency changes by
△
Hz.