4-54
10-12
Feedback Loss Detection Level
Range
【
0 ~ 100
】
¾
10-12 is the level for signal loss. Error = (Set point – Feedback value). When the error is
larger than the loss level setting, the feedback signal is considered lost.
10-13
Feedback Loss Detection Delay Time
Range
【
0.0 ~25.5
】
s
¾
10-13:The minimum time delay before feedback signal loss is determined.
10-14
Integration Limit Value
Range
【
0 ~ 109
】
%
¾
10-14: the Limiter to prevent the PID from saturating.
10-15
Integration Value Resets to Zero
when Feedback Signal Equals
the target
Value
Range
【
0
】
:
Disabled
【
1
】
: After 1 Sec
【
30
】
: After
30 Sec ( Range:- 1 ~ 30 Sec)
¾
10-15=0.As PID feedback value reaches the set point, the integral value will not be reset.
¾
10-15=1~30.As PID feedback value reaches the set point, reset to 0 in 1~30 seconds and
inverter stops. The inverter will run again when the feedback value differs from the set point
value.
10-16
Allowable Integration Error Margin (Unit) (1 Unit = 1/8192)
Range
【
0 ~ 100
】
%
¾
10-16 = 0 ~ 100% unit value: Restart the tolerance after the integrator reset to 0.
10-17
PID
Sleep Frequency Level
Range
【
0.00~650.00
】
Hz
10-18
PID
Sleep Function Delay Time
Range
【
0.0 ~25.5
】
s
10-19
PID
Wake up frequency Level
Range
【
0.00 ~ 650.00
】
Hz
10-20
PID
Wake up function Delay Time
Range
【
0.0 ~ 25.5
】
s
¾
When PID output frequency is less than the sleep threshold frequency and exceeds the time
of sleep delay, the inverter will decelerate to 0 and enters PID sleep mode.
¾
When PID output frequency is larger than the Wake up threshold frequency inverter will
enter the PID mode again as shown in the timing diagram below.
10-18
H z
T
10 -19
10 -17
1 0 -20
W a ke u p
fre q u e n cy
S le e p
fre q u e n cy
P ID o u tp u t fre q u e n cy
A ctu a l o u tp u t fre q u e n cy