4-4
4.1.3 Digital display set up
On power up digital display screens will be as shown below.
MODE
2sec later
Power supply
frequency
parameter
MODE
User selectable display formats:
12- 00
Display Mode
0 0 0 0 0
high
Low
Each of the above 5 digits can be set to any of the selections below from 0 to 7
【
0
】
:Disable display
【
1
】
:output Current
【
2
】
:output Voltage
【
3
】
:DC voltage
【
4
】
:Temperature
【
5
】
:PID feedback
Range
【
6
】
:AVI
【
7
】
:ACI
The highest bit of 12-00 sets the power on the display, other bits set the selected display from range
0-7.as Listed above.
Example1: Set parameter 12- 00=
【
10000
】
to obtain display format shown below.
MODE
MODE
MODE
2sec later
display
:
Power supply
Output Current
Set frequency
parameter