5-27
Cn007
1
0
Speed
Speed reached preset
INS output contact state
Sn215
Value of Zero Speed
Speed
1
0
ZS output contact
5-3-12 Other Functions
When the speed level in CW or CCW directions becomes greater than the value set in
Cn007
(Speed reached preset), the output contact
INS
operates.
Speed reached preset
Parameter
Signal
Name
Default
Unit
Setting Range
Control Mode
Cn007
Speed reached
preset
Rated rpm
× 1/3
rpm 0~4500 S/T
Note: Input contacts status “1” (ON) and “0” (OFF).
Please check section 5-6-1 to set the required high /Low signal levels (PNP/NPN) selection.
Zero Speed preset
When the speed is less than the speed set in Sn215 (Value of ZS), the output contact
ZS
operates.
Parameter
Signal
Name
Default
Unit
Setting Range
Control Mode
Sn215
Value of zero speed
50
rpm
0~4500
S
Note: Input contacts status “1” (ON) and “0” (OFF)
Please check section 5-6-1 to set the required high /Low signal levels (PNP/NPN) selection.