Chapter 5 Trouble shooting and maintenance
5-1
Chapter 5 Troubleshooting and maintenance
5.1Trouble indication and
corrective action
5.1.1
Fault/ Error display and Diagnostics
1.
Un- reset able / un recoverable Errors
Display Error
Cause
Corrective Action
EEPROM
problem
EEPROM problem
Change EEPROM
Over voltage during
stop
Voltage
Detection circuit malfunction
Repair or replace unit
Under voltage
during stop
1. Power voltage too low
2. Restraining resistor or
fuse burnt out.
3. Detection circuit
malfunctions
1. Check if the power voltage is
correct or not
2. Replace the restraining
resistor or the fuse
3.
repair or replace unit
The inverter is
overheated during
stop
1.
Thermal
Detection circuit
malfunction
2. Ambient temperature too
high or bad ventilation
1.
Repair or replace unit
2. Improve ventilation conditions
or relocate inverter
Current
transducer
detection error
Current transducer or
circuit error.
Repair or replace unit
Note: “@” the Failure contact does not operate.
EPR
CTR
OV
@
LV
@
OH
@