Chapter 4 Software index
4-33
C46 (Option card) Multi-function output T+, T-
000:
Run
001: Frequency reached [Preset target frequency ± F23]
002: Frequency reached [ Preset output frequency level (F22) ±F23]
003: Frequency detection (>F22)
004: Frequency detection (<F22)
005: Fault.
006: Auto-restart
007: Momentary power loss
008: Emergency Stop (E.S.)
009: Base Block (b.b.)
010: Motor overload protection
011: Inverter overload protection
012: retain
013: Power ON
014: Communication error
015: Output current detection
Refer to F21 description:
C47 Remote keypad control selection
000: Disable
001: Enable. Operation according to F09
on signal loss
.
002: Enable. Operation at the last set frequency
on signal loss
.
(Stop mode by Inverter keypad or F04 parameter as appropriate).
When C47=001, C49~C53 set parameter disable
the
following parameter
s
will be auto set:
Inverter communication address: No 1 Data bytes: 8 bit
Baud rated (bps): 38400 Parity bytes: no parity
Stop bytes: 1 bit
Note: 1. Connect remote keypad
while
in stop mode,
and the
control priority is with
the
Remote keypad.
2. If the remote keypad is connected in run mode, it will not be effective until the
inverter
has stopped
.
C48 Copy module
000: Copy module Disabled
001: Copy to module from inverter (Read)
002: Copy to inverter from module (write)
003: Read/ write check (Compare the parameters).
Note: Module copy function is applicable only to inverters with the same voltage and KW
rating.
C49 set communication address, for the specific inverter when multi-inverters are controlled by
communication method.
C50 Baud rate (bps)
000: 4800
001: 9600
002: 19200
003: 38400
C49 Inverter communication address: 001~ 254