![TECO F510 series Quick Setting Manual Download Page 95](http://html1.mh-extra.com/html/teco/f510-series/f510-series_quick-setting-manual_1072458095.webp)
A-2
Drive Model F510
Fuse Type
Manufacturer: Bussmann / FERRAZ SHAWMUT
Model
Fuse Ampere Rating (A)
400 V Class Three-Phase Drives
4001
Bussmann 10CT
690V 10A
4002
Bussmann 10CT
690V 10A
4003
Bussmann 16CT
690V 16A
4005
Bussmann 16CT
690V 16A
4008
Bussmann 25ET
690V 25A
4010
Bussmann 40FE
690V 40A
4015
Bussmann 50FE
690V 50A
4020
Bussmann 63FE
690V 63A
4025
Bussmann 80FE
690V 80A
4030
Bussmann 100FE / FERRAZ A50QS100-4
690V 100A / 500V 100A
4040
Bussmann 120FEE
690V 120A
4050
FERRAZ SHAWMUT A50QS150-4
500V 150A
4060
FERRAZ SHAWMUT A50QS200-4 500V
200A
4075
FERRAZ SHAWMUT A50QS250-4 500V
250A
4100 FERRAZ
SHAWMUT
A50QS300-4
500V 300A
4125 FERRAZ
SHAWMUT
A50QS400-4
500V 400A
4150
FERRAZ SHAWMUT A50QS500-4
500V 500A
4175
FERRAZ SHAWMUT A50QS600-4
500V 600A
4215
FERRAZ SHAWMUT A50QS700-4
500V 700A
4250
FERRAZ SHAWMUT A50QS700-4
500V 700A
4300
Bussmann 170M5464
690V 800A
4375
Bussmann 170M5464
690V 800A
4425
Bussmann 170M5466
690V 1000A
◆
Motor Overtemperature Protection
Motor overtemperature protection shall be provided in the end use application.
■
Field Wiring Terminals
All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper
connections that are to be made to each terminal and indicate that copper conductors, rated 75°C are to be used.
■
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow
will not rise above value. Please see electrical ratings for maximum voltage and table below for current.
• The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or greater than the short-
circuit tolerance of the power supply being used.
• Suitable for use on a circuit capable of delivering not more than ( A ) RMS symmetrical amperes for ( Hp ) Hp in 240 / 480 V
class drives motor overload protection.
Horse Power ( Hp )
Current ( A )
Voltage ( V )
1 - 50
5,000
240 / 480
51 - 200
10,000
240 / 480
201 - 400
18,000
240 / 480
401 - 600
30,000
240 / 480