![TECO F510 series Quick Setting Manual Download Page 35](http://html1.mh-extra.com/html/teco/f510-series/f510-series_quick-setting-manual_1072458035.webp)
34
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
message
12-65
~
12-66
Reserved
12-67
Accumulativ
e Energy
(kWHr)
0.0 ~ 999.9
12-68
Accumulativ
e Energy
(MWHr)
0 ~ 60000
12-69
Accumulativ
e Electricity
Price ($)
0 ~ 9999
12-70
Accumulativ
e Electricity
Price
(10000$)
0 ~ 60000
12-71
Flow Meter
Feedback
1 ~ 50000
12-72 RTC Date
12.01.01 ~
99.12.31
12.01.01
12-73 RTC Time 00:00 ~ 23:59
00:00
12-74
Operating
Pressure
Setting
0.01 ~ 25.50
2.00
12-75
Pressure
Feedback
Value
0.01 ~ 25.50
-
12-76
Non-Load
Voltage
0.0 ~ 600.0
-
12-77
Flow Meter
Target
Setting
1 ~ 50000
- *7
12-78 Reserved
12-79
Pulse Input
Percentage
0.0~100.0 -
*7
12-81
Relay Card
Display
ON: LCD
display is 1
OFF: LCD
display is 0
-
Note5
12-82
Motor Load 0 ~ 200.0
-
Note6
* Models of inverter ratings above 200V 60HP
(including 60HP) and 400V 100HP (including
100HP) in IP20 enclosure do not support
functions of heatsink temperature display. All
models in IP55 enclosure support functions of
heatsink temperature display.
* Maximum upper limit in motor speed (rpm) of
parameter 12-22 is
65534.
Group 13 Maintenance Function Group
Code
Parameter
Name
Setting Range Default
Attribu
te
13-00
Inverter
Rating
Selection
00H~FFH -
*4
13-01
Software
Version
0.00-9.99 -
*4
Group 13 Maintenance Function Group
Code
Parameter
Name
Setting Range Default
Attribu
te
13-02
Clear
Cumulative
Operation
Hours
Function
0: Disable to
Clear
Cumulative
Operation
Hours
1: Clear
Cumulative
Operation
Hours
0
*1
13-03
Cumulative
Operation
Hours 1
0~23 -
*4
13-04
Cumulative
Operation
Hours 2
0~65534 -
*4
13-05
Selection of
Accumulativ
e Operation
Time
0:
Accumulative
time in power on
0 *1
1:
Accumulative
time in operation
13-06
Parameters
Locked
0: Only
parameter 13-
06 and
frequency
setting
parameters in
main screen
are writable
2 *1
1: Only user
parameter is
enabled.
2: All
parameters are
writable.
13-07
Parameter
Password
Function
00000~65534 00000
13-08
Restore
Factory
Setting
0: No
Initialization
0
2: 2 wire
Initialization
(220/440V,
60Hz)
3: 3 wire
Initialization
(220/440V,
60Hz)
4: 2 wire
Initialization
(230/415V,
50Hz)
5: 3 wire
Initialization
(230/415V,
50Hz)
6: 2 wire
Initialization
(200/380V,
50Hz)
7: 3 wire
Initialization
(200/380V,
50Hz)
Summary of Contents for F510 series
Page 1: ......
Page 56: ...2 1 4 1 5 08 30 07 00 5 5 20Hp 15 1 6 25 10 40 60 95 RH...
Page 57: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Page 58: ...4 2 2 F510 F510 2 1 2 2 2 3...
Page 100: ......