![TECO F510 series Quick Setting Manual Download Page 12](http://html1.mh-extra.com/html/teco/f510-series/f510-series_quick-setting-manual_1072458012.webp)
11
Group 00 Basic Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
00-00
Control
Mode
Selection
0: V/F
0 *3
1: Reserved
2: SLV
3~4: Reserved
5: PM SLV
00-01
Motor’s
Rotation
Direction
0: Forward
0 *1
1: Reverse
00-02
Main Run
Command
Source
Selection
0: Keypad
1
1: External
Terminal
(Control
Circuit)
2:
Communication
Control (RS-
485)
3: PLC
4: RTC
00-03
Alternative
Run
Command
Source
Selection
0: Keypad
0
1: External
Terminal
(Control Circuit)
2:
Communicatio
n Control (RS-
485)
3: PLC
4: RTC
00-04
Language
Selection
(for LCD
only)
0: English
0
1: Simple
Chinese
2: Traditional
Chinese
3: Turkish
00-05
Main
Frequency
Command
Source
Selection
0: Keypad
1
1: External
Terminal
(Analog AI1)
2: Terminal
Command
UP/ DOWN
3:
Communicatio
n Control (RS-
485)
4: Reserved
5: Reserved
6: RTC
7. AI2 Auxiliary
Frequency
*7
00-06
Alternative
Frequency
Command
Source
Selection
0: Keypad
0
1: External
Terminal
(Analog)
2: Terminal
Command
Group 00 Basic Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
UP/ DOWN
3:
Communication
Control (RS-
485)
4: Reserved
5: Reserved
6: RTC
7. AI2 Auxiliary
Frequency
*7
00-07
Main and
Alternative
Frequency
Command
Modes
0: Main
Frequency
0
1: Main
Fre
Alternative
Frequency
00-08
Communica
tion
Frequency
Command
Range
0.00-400.00 0.00
00-09
Communica
tion
Frequency
Command
Memory
Selection
0: Do not save
when power
is off.
0
1: Save when
power is off.
00-10
Minimum
frequency
detection
0: Show
warning if
lower than
minimum
frequency
1: Run as
minimum
frequency if
lower than
minimum
frequency
0
Note2
00-11
Selection of
PID Lower
Limit
Frequency
0: PID is bound
to lower limit
frequency
when
inverter
sleeps.
0
Note1
1: PID is bound
to 0Hz when
inverter
sleeps.
00-12
Upper Limit
Frequency
0.1~109.0 100.0
00-13
Lower Limit
Frequency
0.0~109.0 0.0
00-14
Acceleration
Time 1
0.1~6000.0 - *1
00-15
Deceleratio
n Time 1
0.1~6000.0 -
*1
00-16
Acceleration
Time 2
0.1~6000.0 - *1