Group 09: Communication Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
to Stop Based
on Deceleration
Time 2 when
Communication
Fault Occurs.
3: Keep
Operating
when
Communication
Fault Occurs.
4: Run the
Frequency
Command
given by AI2
09-08
Comm.
Fault
Tolerance
Count
1~20 1
09-09
Waiting
Time
5~65 5
09-10
Device
Instance
Number
1 ~ 254
1
Note: Parameters in group 09 are not affected by
parameter 13-08 (initialization).
Note: Selection of item 4 in parameter 09-01 is
required to be coupled with the Profibus card.
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
10-00
PID Target
Value
Source
Setting
0: PUMP or
HVAC
function
given (refer
to group 23)
1
1: AI1 Given
2: AI2 Given
3: Reserved
4: 10-02 Given
5: Reserved
Note
6: Frequency
Command
(00-05)
Note
7:
Multi-speed
Frequency
Command
10-01
PID
Feedback
Value
Source
Setting
1: AI1 Given
2
2: AI2 Given
3: Reserved
4: AI1 - AI2
Given
10-02
PID Target
Value
0.0~100.0 0.0
10-03
PID Control
Mode
xxx0b: PID
Disable
0000b
xxx1b: PID
Enable
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
xx0xb: PID
Positive
Characteristic
xx1xb: PID
Negative
Characteristic
x0xxb: PID
Error Value of
D Control
x1xxb: PID
Feedback
Value of D
Control
0xxxb: PID
Output
1xxxb: PID
Frequency
Command
10-04
Feedback
Gain
0.01~10.00 1.00
*1
10-05
Proportional
Gain (P)
0.00~10.00 3.00
*1
10-06
Integral
Time (I)
0.00~100.00 0.50
*1
10-07
Differential
Time (D)
0.00~10.00 0.00
*1
10-08
Reserved
10-09 PID Bias
-100.0~100.0
0
*1
10-10
PID Primary
Delay Time
0.00~10.00 0.00
*1
10-11
PID
Feedback
Loss
Detection
Selection
0: Disable
0
1: Warning
2: Fault
10-12
PID
Feedback
Loss
Detection
Level
0~100 0
10-13
PID
Feedback
Loss
Detection
Time
0.0~10.0 1.0
10-14
PID Integral
Limit
0.0~100.0 100.0
*1
10-15
10-16
Reserved
10-17
Start
Frequency
of PID
Sleep
0.00~400.00 30.00
10-18
Delay Time
of PID
Sleep
0.0~255.5
0.0
10-19
Frequency
of PID
0.00~400.00 0.00