![TECO F510 series Quick Setting Manual Download Page 44](http://html1.mh-extra.com/html/teco/f510-series/f510-series_quick-setting-manual_1072458044.webp)
43
Group 23 Pump & HVAC Function
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
23-00
Function
Selection
0: Disable
0 *7
1: Pump
2: HVAC
3: Compressor
*7
23-01
Setting of
Single &
Multiple
Pumps and
Master &
Slave
Machines
0: Single Pump
0
1: Master
2: Slave 1
3: Slave 2
4: Slave 3
23-02
Operation
Pressure
Setting
0.10 ~ 650.00
4.00
*6
23-03
Maximum
Pressure of
Pressure
Transmitter
0.10 ~ 650.00
10.00
*6
23-04
Pump
Pressure
Command
Source
0: Set by 23-02
0
1: Set by AI
23-05
Display
Mode
Selection
0: Display of
Target and
Pressure
Feedback *
0
1: Only Display
Target
Pressure
2: Only Display
Feedback
Pressure
23-06
Proportion
Gain (P)
0.00~10.00 3.00
23-07
Integral
Time (I)
0.0~100.0 0.5
23-08
Differential
Time (D)
0.00~10.00 0.00
23-09
Tolerance
Range of
Constant
Pressure
23-20=0 : 0.01
~ 650.00
23-20=1 :
1~100
5 *6
23-10
Sleep
Frequency
of Constant
Pressure
0.00 ~ 400.00
30.00
23-11
Sleep Time
of Constant
Pressure
0.0 ~ 255.5
0.0
23-12
Maximum
Pressure
Limit
23-20=0 : 0.00
~ 650.00
23-20=1 :
0~100
50 *6
23-13
Warning
Time of
High
Pressure
0.0 ~ 600.0
10.0
23-14 Stop Time 0.0 ~ 600.0
20.0
Group 23 Pump & HVAC Function
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
of High
Pressure
23-15
Minimum
Pressure
Limit
23-20=0 : 0.00
~ 650.00
23-20=1 :
0~100
5 *6
23-16
Warning
Time of Low
Pressure
0.0 ~ 600.0
0.0
23-17
Fault Stop
Time of Low
Pressure
0.0 ~ 600.0
0.0
23-18
Detection
Time of
Loss
Pressure
0.0 ~ 600.0
0.0
23-19
Detection
Proportion
of Loss
Pressure
0 ~ 100
0
23-20
Switching of
Pressure
and
Percentage
0:Pressure
1
Note4
1:Percentage
23-21
Reserved
23-22
Slave
Escape
Frequency
0.00 ~ 400.00
45.00
Note2
23-23
Direction of
Water
Pressure
Detection
0: Upward
Detection
1
1: Downward
Detection
23-24
Range of
Water
Pressure
Detection
23-20=0 : 0.00
~ 65.00
23-20=1 : 0~10
1 *6
23-25
Period of
Water
Pressure
Detection
0.0 ~ 200.0
30.0
23-26
Acceleration
Time of
Water
Pressure
Detection
0.1 ~ 6000.0
KVA
23-27
Deceleratio
n Time of
Water
Pressure
Detection
0.1 ~ 6000.0
KVA
23-28
Forced Run
Command
0.00 ~400.00
0.00
23-29
Switching
Time of
Multiple
Pumps in
Parallel
0 ~ 240
3
Summary of Contents for F510 series
Page 1: ......
Page 56: ...2 1 4 1 5 08 30 07 00 5 5 20Hp 15 1 6 25 10 40 60 95 RH...
Page 57: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Page 58: ...4 2 2 F510 F510 2 1 2 2 2 3...
Page 100: ......