6
2.3 General Wiring Diagram (For Enhanced E & G type)
Notes:
*1: Models 200V 1 ~ 25HP and 400V 1 ~ 30HP or lower ratings have a built-in braking transistor. To use this braking
transistor a braking resistor can be connected between B1 and B2.
*2: Use SW6 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function
digital input terminals S1~S8.
*3: Use SW3/SW4 to switch between voltage (0~10V) and current (4~20mA) input for Multi-function analog input 2 (AI2).
Besides please also check parameter 04-00 for proper setting.
*4: Run Permissive input SF1 and SF2 is a normally closed input. This input should be closed to enable the inverter
output. To activate this input remove the jumper wire between SF1/ SF2 and SG.
*5: When using the open collector for pulse input, it doesn’t need resistance because of built-in pull-up resistance.
*6: AO1/AO2 default setting is 0~+10V.
*7: Both 200V class 50HP~150HP and 400V class 100HP~425HP have built-in DC reactors.
*8: It need turn on the switch for the terminal resistor RS485 in the last inverter when many inverters in parallel
connection.