50
Group 22: PM Motor Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
22-39
Preliminary DC
injection time
0~20.00 0.10
22-40
High frequency
angle finding
time
0.01~1.00 0.01
22-41
PM stop
method
0: Decelerate
or stop below
22-11 and
brake directly
1: Decelerate
or stop below
22-11 and
open loop
stop
0
22-42
Fully closed
loop control
gain Ka
64~8192 100
22-43
Fully closed
loop control
gain Kb
64~8192 2000
22-44
Fully closed
loop control
gain speed low
pass filter
1~256 4
22-45
Fully closed
loop control
magnetic flux
0.01~10.00 0.70
.
Chapter 4 Troubleshooting
and Fault Diagnostics
4.1 General
Inverter fault detection and early warning / self-
diagnosis function. When the inverter detects a
fault, a fault message is displayed on the
keypad. The fault contact output energizes and
the motor will coast to stop (The stop method
can be selected for specific faults).
When the inverter detects a warning / self-
diagnostics error, the digital operator will
display a warning or self-diagnostic code, the
fault output does not energize in this case.
Once the warning is removed, the system will
automatically return to its original state.
4.2 Fault Detection Function
When a fault occurs, please refer to Table 4.1
for possible causes and take appropriate
measures.
Use one of the following methods to restart:
1. Set one of multi-function digital input
terminals (03-00, 03-07) to 17 (Fault reset);
activate input
2. Press the reset button on the keypad.
3. Power down inverter wait until keypad goes
blank and power-up the inverter again.
When a fault occurs, the fault message is
stored in the fault history (see group 12
parameters).
Table 4.1 Fault information and possible
solutions
LED display
Possible solutions
OC
over current
Extend acceleration /
deceleration time.
Check the motor wiring.
Disconnect motor and try
running inverter.
OCA
over current
Set the longer acceleration
time
Change to bigger capacity
of inverter
Examine motor
Check the wire
Replace IGBT module
OCC
over current
Change to bigger capacity
of inverter
Add reactor to power
source
OCd
over current
Set the longer acceleration
time
SC
short circuit
Check the motor wiring.
Disconnect motor and try
running inverter.
GF
Ground fault
Replace motor.
Check the motor wiring.
Disconnect motor and try
running inverter.
Check resistance
between cables and
ground.
Reduce carrier frequency.
OV
Over voltage
Increase deceleration
time
Summary of Contents for A510s