A-4
Motor Over-temperature Protection
Motor over temperature protection is not provided.
Motor over-temperature protection shall be provided in the end use application.
■
Field Wiring Terminals
All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the
proper connections that are to be made to each terminal and indicate that copper conductors, rated 75°C
are to be used.
■
Inverter Short-Circuit Rating
This inverter has undergone the UL short-circuit test, which certifies that during a short circuit in the power
supply the current flow will not rise above value. Please see electrical ratings for maximum voltage and
table below for current.
• The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or
greater than the short-circuit tolerance of the power supply being used.
• Suitable for use on a circuit capable of delivering not more than (A) RMS symmetrical amperes
for.DiJ2.lHp in 240 / 480 V class drives motor overload protection.