27
Group 06: Automatic Program Operation
Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Speed-Stage
12
06-45
Operation
Direction
Selection of
Speed-Stage
13
0: Stop
1: Forward
2: Reverse
0
06-46
Operation
Direction
Selection of
Speed-Stage
14
0: Stop
1: Forward
2: Reverse
0
06-47
Operation
Direction
Selection of
Speed-Stage
15
0: Stop
1: Forward
2: Reverse
0
* If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to 0.1Hz
Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
07-00
Momentary
Power
Loss/Fault
Restart
Selection
0: Disable
0
1: Enable
07-01
Fault Auto-
Restart Time
0~7200 0
07-02
Number of
Fault Auto-
Restart
Attempts
0~10 0
07-03 Reserved
07-04
Direct Start at
Power on
0: When the
external run
command is
enabled, direct
start at power up
1
1: When the
external run
command is
enabled, unable
to direct start at
power-up.
07-05
Delay of
Direct Start at
Power on
1.0~300.0 3.5
07-06
DC Injection
Braking
Starting
Frequency
0.0~10.0 0.5
07-07
DC Injection
Braking
Current
0~100 50
07-08 DC Injection
0.00~100.00
0.50
Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
Braking Time
at Stop
07-09
Stop Mode
Selection
0: Deceleration
to Stop
0
1: Coast to Stop
2: DC Braking
Stop in All
Fields
3: Coast to Stop
with Timer
07-10
~
07-12
Reserved
07-13
Low Voltage
Detection
Level
200V: 150~300
190
400V: 250~600
380
575V: 500~600
546
690V: 500~600
546
07-14
Pre-excitation
Time
0.00~10.00 2.00
07-15
Pre-excitation
Level
50~200 100
07-16
DC Injection
Braking Time
at Start
0.00~100.00 0.00
07-17
Reserved
07-18
Minimum
Base block
Time
0.1~5.0 -
07-19
Direction-
Detection
Speed
Search
Operating
Current
0~100 50
07-20
Speed
Search
Operating
Current
0~100 20
07-21
Integral Time
of Speed
Searching
0.1~10.0 2.0
07-22
Delay Time of
Speed
Searching
0.0~20.0 0.2
07-23
Voltage
Recovery
Time
0.1~5.0 2.0
07-24
Direction-
Detection
Speed
Search
Selection
0: Disable
1
1: Enable
07-25
Low Voltage
Detection
Time
0.00~1.00 0.02
07-26
Start-up Mode
Selection of
SLV Coast to
Stop
0: Start with
speed search
0
1: Normal start
Summary of Contents for A510s
Page 1: ......
Page 60: ...2 1 4 1 5 11 55 07 00 5 5 15Hp 15 1 6 25 14 104 140 F 10 40 60 C 95 RH...
Page 61: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Page 111: ......