15
Group 00: Basic Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
00-18
*Jog
Frequency
0.00~599.00 6.00
*1
00-19
Jog
Acceleration
Time
0.1~0600.0 -
*1
00-20
Jog
Deceleration
Time
0.1~0600.0 -
*1
00-21
Acceleration
time 3
0.1~6000.0 *
*1
00-22
Deceleration
time 3
0.1~6000.0 *
*1
00-23
Acceleration
time 4
0.1~6000.0 *
*1
00-24
Deceleration
time 4
0.1~6000.0 *
*1
00-25
Switch-Over
Frequency of
Acc/Dec Time
1 and Time 4
0.00~599.00 0.0
00-26
Emergency
Stop Time
0.1~6000.0 5.0
00-27
HD/ND Mode
Selection
***
0: HD (Heavy
Duty Mode)
0 *3
1: ND (Normal
Duty Mode)
00-28
Command
Characteristic
selection of
master
frequency
0: Positive
Characteristic
(0~10V/4~20mA
is corresponding
to 0~100%)
0
1: Negative
Characteristic
(0~10V/4~20mA
is corresponding
to 100~0%)
00-29
Zero-Speed
Operation
Selection
0: Operation
Based on
Frequency
Command
0
1: Stop
2: Operation
Based on the
Lowest
Frequency
3: Zero-Speed
Operation
00-30
00-31
Reserved
00-32
Application
Selection
Presets**
0: General
0
1: Reserved
2: Conveyor
3: Exhaust Fan
4: Reserved
5: Compressor
6: Hoist**
7: Crane**
Group 00: Basic Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
8: Manual Pulse
Generator
(MPG)
(Note4)
9: Band Saw
10: Stamping
Press
00-33
Modified
Parameters
(only for LCD
keypad)
0:Disable
0 *7
1:Enable
00-34
~
00-40
Reserved
00-41
User
parameter 0
Set 13-06 = 1,
start user
parameter. The
setting range is
00-01 ~22-31,
but except 00-
41~00-56 and
group 17 (only
for LCD keypad)
00-41
*7
00-42
User
parameter 1
00-42
*7
00-43
User
parameter 2
00-43
*7
00-44
User
parameter 3
00-44
*7
00-45
User
parameter 4
00-45
*7
00-46
User
parameter 5
00-46
*7
00-47
User
parameter 6
00-47
*7
00-48
User
parameter 7
00-48
*7
00-49
User
parameter 8
00-49
*7
00-50
User
parameter 9
00-50
*7
00-51
User
parameter 10
00-51
*7
00-52
User
parameter 11
00-52
*7
00-53
User
parameter 12
00-53
*7
00-54
User
parameter 13
00-54
*7
00-55
User
parameter 14
00-55
*7
00-56
User
parameter 15
00-56
*7
00-57
SV High
Speed Mode
0: SV High
Speed Mode1
0
1: SV High
Speed Mode2
*: Refer to the attachment 1 in our instruction manual.
**: Before to set up 00-32 Application, it should do
initialized setting (parameter 13-08) first. When
setting 00-32, the I/O port function changed
automatically. To avoid accident, be sure to confirm
the I/O port signal of inverter and external terminal
control.
Summary of Contents for A510s
Page 1: ......
Page 60: ...2 1 4 1 5 11 55 07 00 5 5 15Hp 15 1 6 25 14 104 140 F 10 40 60 C 95 RH...
Page 61: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Page 111: ......