Summary of Contents for A510s

Page 1: ......

Page 2: ...ect to IEC 61800 3 In a domestic environment this product may cause radio interference in which case the user may need to apply corrective measures Motor over temperature protection is provided 1 2 Wi...

Page 3: ...arameters Setting Caution Do not connect a load to the motor while performing a rotational auto tune Make sure the motor can freely run and there is sufficient space around the motor when performing a...

Page 4: ...form maintenance inspection and replacement operations Take off metal jewelry such as watches and rings and use insulated tools Caution The Inverter can be used in an environment with a temperature ra...

Page 5: ...er install a magnetic contactor Do not use the magnetic contactor as the run stop switch for the inverter AC line reactor for power quality When inverters are supplied by a high capacity power source...

Page 6: ...for proper setting 4 Run Permissive input F1 and F2 is a normally closed input This input should be closed to enable the inverter output To activate this input remove the jumper wire between F1 and F2...

Page 7: ...Multi function analog input 2 AI2 Besides please also check parameter 04 00 for proper setting 4 Run Permissive input SF1 and SF2 is a normally closed input This input should be closed to enable the i...

Page 8: ...1 Input Power Supply For single phase use terminals R L1 and S L2 S L2 T L3 B1 P B1 P B2 external braking resistor B2 DC power supply U T1 Inverter output V T2 W T3 E Ground terminal 2 5 General Power...

Page 9: ...default 1 24V Power supply 24V Digital signal SOURCE point SW3 switched to SOURCE 15 Max output current 250mA The sum of all loads connected 24VG Common terminal of Digital signals Common point of di...

Page 10: ...2HP 400V 1 3HP DOG Open collector transistor digital ground Relay output R1A Relay A contact multi function output terminal Relay B contact multi function output terminal Relay contact common termina...

Page 11: ...W6 switched to SINK Analog input signal 10V Positive power for external speed potentiometer 10V Max current 20mA 10V Negative power for external speed potentiometer 10V Max current 20mA AI1 Multi func...

Page 12: ...erminal With the same functions as DO1 Rating 250Vac 10 mA 1A 30Vdc 10 mA 1A Run Permiss ive Input SF1 SF2 On normal operation Off stop Jumper wired between SF1 SF2 and SG has to be removed by using e...

Page 13: ...4300 4375 4425 requires the user to select the correct jumper position based on the inverter input voltage 440V is the default position for these models Please select the correct position according t...

Page 14: ...trol Parameters Group 22 PM Motor Parameters Parameter Attribute 1 Parameters can be changed during run operation Note1 New added or modified parameters in software V1 02 Note2 New added or modified p...

Page 15: ...tion 0 Keypad 0 Note4 1 External Terminal Analog 1 Group 00 Basic Parameters Code Parameter Name Setting Range Default Attrib ute 2 Terminal Command UP DOWN 3 Communication Control RS 485 4 Pulse Inpu...

Page 16: ...Group 00 Basic Parameters Code Parameter Name Setting Range Default Attrib ute 8 Manual Pulse Generator MPG Note4 9 Band Saw 10 Stamping Press 00 33 Modified Parameters only for LCD keypad 0 Disable...

Page 17: ...age of Motor 1 200V 0 0 255 0 7 5 8 400V 0 0 510 0 15 0 575V 0 0 670 0 690V 0 0 804 0 01 10 Torque Compensatio n Gain 0 0 2 0 0 5 1 01 11 Selection of Torque 0 Torque Compensation 0 Group 01 V F Contr...

Page 18: ...oefficient 3 of Motor 1 80 300 02 13 Core loss of Motor 1 0 0 15 0 02 14 Reserved 02 15 Resistance between Wires of Motor 1 0 001 60 000 Group 02 IM Motor Parameters Code Parameter Name Setting Range...

Page 19: ...and rotation freely to stop 16 PID Control Disable 17 Fault Reset RESET 18 Reserved Group 03 External Digital Input and Output Parameters Code Parameter Name Setting Range Default Attrib ute 19 Speed...

Page 20: ...tor Mode Switch Note4 68 External Fault 2 Note4 69 External Overload Note4 03 08 S1 S8 DI Scan Time 0 Scan Time 4ms 1 Scan Time 8ms 1 03 09 Multi Function Terminal S1 xxx0b S1 A Contact 0000b Group 03...

Page 21: ...gree Position Mode 42 44 Reserved 45 PID sleep Group 03 External Digital Input and Output Parameters Code Parameter Name Setting Range Default Attrib ute 46 49 Reserved 50 Frequency Detection 3 03 44...

Page 22: ...4 Filter Time of Pulse Input 0 00 2 00 0 1 1 03 35 Function Setting of Pulse Output 1 Frequency Command 2 1 2 Output Group 03 External Digital Input and Output Parameters Code Parameter Name Setting R...

Page 23: ...ncy Reference Bias 3 Output Voltage Bias 4 Coefficient of Acceleration and Deceleration Reduction 5 DC Braking Current 6 Over Torque Detection Level 7 Stall Prevention Level During Running 8 Frequency...

Page 24: ...eleration and Deceleration Selection of Multi Speed 0 Acceleration and deceleration time are set by 00 14 00 24 0 1 Acceleration and Deceleration Time are set by 05 17 05 48 05 01 Frequency Setting of...

Page 25: ...0 10 0 05 31 Acceleration Time Setting of Multi Speed 7 0 1 6000 0 10 0 05 32 Deceleration 0 1 6000 0 10 0 Group 05 Multi Speed Parameters Code Parameter Name Setting Range Default Attrib ute Time Se...

Page 26: ...n the speed of stage 0 6 After the completion of a single cycle the on going operation speed is based on the speed of the last stage Restart speed is based on the speed of stage 0 Group 06 Automatic P...

Page 27: ...tion Parameters Code Parameter Name Setting Range Default Attrib ute of Speed Stage 13 06 30 Operation Time Setting of Speed Stage 14 0 0 6000 0 0 0 1 06 31 Operation Time Setting of Speed Stage 15 0...

Page 28: ...0 3 5 07 06 DC Injection Braking Starting Frequency 0 0 10 0 0 5 07 07 DC Injection Braking Current 0 100 50 07 08 DC Injection 0 00 100 00 0 50 Group 07 Start Stop Parameters Code Parameter Name Set...

Page 29: ...on 0 STP2 Enable 0 Note4 1 STP2 Disable 07 46 DC Injection 0 150 100 Note5 Group 07 Start Stop Parameters Code Parameter Name Setting Range Default Attrib ute Current Limit 07 47 PM Speed Switching Fr...

Page 30: ...08 12 Reserved 08 13 Selection of Over Torque Detection 0 Over Torque Detection is Disabled 0 1 Start to Detect when Reaching the Set Frequency Group 08 Protection Parameters Code Parameter Name Setti...

Page 31: ...meters Code Parameter Name Setting Range Default Attrib ute Prevention Limit 08 42 PTC Protection Level 0 1 10 0V 0 7 08 43 PTC Restart Level 0 1 10 0V 0 3 08 44 PTC Warning Level 0 1 10 0V 0 5 08 45...

Page 32: ...urs 2 Deceleration to Stop Based on Deceleration Time 2 when Communication Fault Occurs 3 Keep Operating when Communication Fault Occurs 09 08 Comm Fault 1 20 1 3 Group 09 Communication Parameters Cod...

Page 33: ...D Target Acceleration Deceleration Time 0 0 25 5 0 0 10 27 PID Feedback Display Bias 0 9999 0 10 28 Reserved 10 29 PID Sleep Selection 0 Disable 1 1 Enable 2 set by DI 10 30 Upper Limit of PID Target...

Page 34: ...Gain 0 100 80 11 13 Automatic Return Time 0 120 60 1 11 14 11 17 Reserved Group 11 Auxiliary Parameters Code Parameter Name Setting Range Default Attrib ute 11 18 Manual Energy Saving Frequency 0 0 59...

Page 35: ...me at Stop 0 0 10 0 0 0 11 47 KEB Deceleration Time 0 0 25 5 0 0 1 11 48 KEB Detection Level 200V 190 210 200 400V 380 420 400 575V 540 570 555 690V 540 684 555 11 49 Zero servo Gain 0 01 5 00 1 00 Gr...

Page 36: ...utton Selection 0 Forward Reverse control 1 Local Remote control 1 11 81 OVP4 Level 100 200 110 Group 11 Auxiliary Parameters Code Parameter Name Setting Range Default Attrib ute 11 82 OVP4 Gain 0 256...

Page 37: ...nge Default Attrib ute current fault 12 16 Frequency Command If LED enters this parameter it only allows monitoring frequency command 12 17 Output Frequency Display the current output frequency 12 18...

Page 38: ...Setting Range Default Attrib ute values of 20 27 12 36 PID Input Display input error of the PID controller PID target value PID feedback 100 corresponds to the maximum frequency set by 01 02 or 01 16...

Page 39: ...ilar to 12 05 12 60 Inverter Status of Previous Fault Display inverter status of previous fault Description is similar to 12 43 12 61 Trip Time 1 of Last Fault Display the operation time of last time...

Page 40: ...5V 7 3 wire initialization 50HZ 200 380V Group 13 Maintenance Parameters Code Parameter Name Setting Range Default Attrib ute 575V 8 PLC initialization 9 2 wire Initialization 60Hz 230 460V 10 3 wire...

Page 41: ...tory Exhibit Previous twenty Fault History Note1 13 41 Previous twenty one Exhibit Previous Note1 Group 13 Maintenance Parameters Code Parameter Name Setting Range Default Attrib ute Fault History twe...

Page 42: ...et Value 1 0 65534 Note4 1 Note6 14 46 MD4 Set Value 2 0 65534 Note4 1 Note6 14 47 MD4 Set Value 3 0 65534 Note4 1 Note6 Group 15 PLC Monitoring Parameters Code Parameter Name Setting Range Default At...

Page 43: ...y of XXX X at 100 20001 29999 Users specify the format Input 2XXXX represents the display of XX XX at 100 30001 39999 Users specify the format Input 3XXXX Group 16 LCD Function Parameters Code Paramet...

Page 44: ...e 1 Mon 2 Tue 3 Wed 4 Thu 5 Fri 6 Sat 7 Sun 1 Note8 16 25 P3 Stop Date 5 Note8 16 26 P4 Start Time 00 00 23 59 08 00 Note8 16 27 P4 Stop Time 00 00 23 59 18 00 Note8 16 28 P4 Start Date 1 Mon 2 Tue 3...

Page 45: ...99 0 50 0 Group 17 Automatic Tuning Parameters Code Parameter Name Setting Range Default Attrib ute Frequency 60 0 17 05 Motor Rated Speed 0 24000 KVA 17 06 Pole Number of Motor 2 16 Even 4 17 07 PG P...

Page 46: ...0 0 0 1 19 03 Jump Time of Wobble Frequency 0 50 0 1 19 04 Wobble 0 0 1000 0 10 0 1 Group 19 Wobble Frequency Parameters Code Parameter Name Setting Range Default Attrib ute Frequency Cycle 19 05 Wob...

Page 47: ...999 1024 20 28 Selection of PG Rotation Direction 0 Forward as Counter Clockwise Rotation 0 Group 20 Speed Control Parameters Code Parameter Name Setting Range Default Attrib ute 1 Forward as Clockwis...

Page 48: ...The Command of Rotation Cycle Number of Section 5 9999 9999 0 21 21 The Command of the Pulse 9999 9999 0 Group 21 Torque And Position Control Parameters Code Parameter Name Setting Range Default Attr...

Page 49: ...rrent 25 200 inverter s rated current KVA 22 03 PM Motor s Pole Number 2 96 6 22 04 PM Motor s Rotation Speed 6 60000 1500 Group 22 PM Motor Parameters Code Parameter Name Setting Range Default Attrib...

Page 50: ...w Speed High Frequency Estimate 0 Group 22 PM Motor Parameters Code Parameter Name Setting Range Default Attrib ute Control 2 Full Closed Loop Control 22 27 Voltage Command of Mode 2 5 120 Note7 22 25...

Page 51: ...will automatically return to its original state 4 2 Fault Detection Function When a fault occurs please refer to Table 4 1 for possible causes and take appropriate measures Use one of the following me...

Page 52: ...y cycle OT Over torque detection Check over torque detection parameters 08 15 08 16 Check and reduce motor load check and operation duty cycle UT Under torque detection Check under torque detection pa...

Page 53: ...ct Replace the control board CTER CT Failure Check current transformer signal and the voltage on the control board CF20 Communication Failure Check only use one kind of communication type Protection F...

Page 54: ...ed search parameters UV flash under voltage Check the input voltage Check input wiring Increase acceleration time Check power source Replace pre charge contactor Replace control board or complete inve...

Page 55: ...r overload Check V f curve Replace inverter with larger rating Check and reduce motor load check and operation duty cycle CE flash communication error Check connection Check host computer software LED...

Page 56: ...Type 22 08 and power on again SE08 PM Motor mode error Check control mode SE09 PI setting error Check pulse input selection 03 30 and PID source 10 00 and 10 01 FB flash PID feedback breaking Check f...

Page 57: ...r 17 11 Note The fault contact output does not energize with an auto tuning fault Refer to Table 4 3 for fault information during tuning cause and corrective action Table 4 3 Auto tuning fault and cor...

Page 58: ...uring magnetic pole alignment during rotational auto tune Check motor Check motor wiring Check brake released 05 Circuit tuning time out Check for active protection functions preventing auto tuning 06...

Page 59: ...1 1 1 1 R L1 S L2 R L1 S L2 T L3 U T1 V T2 W T3 40 50 IEC 61800 3 1 2 220V 100 440V 10 EN61800 5 1 10mm2 6AWG RCD B LC RC 1 3 13 00 25 11 01...

Page 60: ...2 1 4 1 5 11 55 07 00 5 5 15Hp 15 1 6 25 14 104 140 F 10 40 60 C 95 RH...

Page 61: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...

Page 62: ...N 1 2 100 1 2 AO1 DC 0 10V AO2 DC 0 10V 4 20mA PG 250VAC 1A 30VDC 1A DC 48V 50mA Open Collector 32k Hz Max GND DO1 P 2 1 3 5 6 5 1 200V 1 25HP 400V 1 40HP B2 B1 B2 2 S1 S8 SW3 Source PNP with 24V comm...

Page 63: ...1 B2 2 S1 S8 SW6 Source PNP with 24V common or Sink NPN with 24VG common 3 AI1 AI2 SW3 SW4 0 10V 10 10V 4 20mA 04 00 4 SF1 SF2 SG SF1 SG SF2 SG 5 pull up 6 AO1 AO2 0 10V 7 RS485 8 200V 3 40HP 400V 5 7...

Page 64: ...25HP 400V 1 40HP 200V 30 150HP 400V 50 425HP R L1 R S S L2 T L3 B1 P B1 P B2 B2 U T1 V T2 W T3 E 200V 1 2HP 400V 1 3HP 200V 3 40HP 400V 5 75HP R1A R1B R1C R2A R2C RJ45 200V 50 150HP 400V 100 425HP R2...

Page 65: ...440V 5HP 10V 20mA AI1 0 10V 10V 10V 0 10V 10V 10V 20K 11bit 1 AI2 2 SW2 0 10V 4 20mA 0 10V 10V 10V 200K 4 20 mA 250 11 bit 1 GND E AO1 3 0 10V 0 10V 2mA 4 20 mA 500 PWM 10KHz AO2 3 SW6 0 10V 4 20mA G...

Page 66: ...DO2 250Vac 10 mA 1A 30Vdc 10 mA 1A R1B R1C R2A R2C 200V 3HP 400V 5HP DO1 DO2 250Vac 10 mA 1A 30Vdc 10 mA 1A F1 24Vdc 8mA pull high F2 24V Ground RS 485 S RS485 MODBUS S E G 1 03 2 04 3 04 10V 20mA AO1...

Page 67: ...type 3 200V 1 30HP 400V 1 75HP 200V 40 150HP 400V 100 425HP R L1 R S S L2 T L3 P1 P2 B1 B2 P1 P2 B1 DCL 2 5 P2 B1 B2 U T1 V T2 W T3 E 200V 1 2HP 400V 1 3HP 200V 3 40HP 400V 5 75HP 200V 50 150HP 400V...

Page 68: ...0V 20mA 10V 10V 20mA AI1 2 SW3 10V 10V 4 20mA 0 10V 10V 10V 500K 4 20 mA 500 11bit 1 AI2 2 SW4 0 10V 4 20mA 0 10V 900K 4 20 mA 250 11 bit 1 GND E AO1 3 SW1 0 10V 4 20mA 0 10V 2mA 4 20 mA 500 PWM 10KHz...

Page 69: ...400V 380V 480V 150HP 425HP 440V 400V 1 400V 150HP 215HP 2 400V 270HP 425HP 4KA69X571W01 4P108C0010103 VER 04 DM1 25CN 36CN 32CN 31CN 33CN 34CN 35CN 2 FU1 220V 440V S R TB3 1 220V 26CN 440V TB4 220V 38...

Page 70: ...0 01 V F 02 IM 03 04 05 06 07 08 09 10 PID 11 12 13 14 PLC 15 PLC 16 LCD 17 18 19 20 21 22 PM 1 1 1 02 2 1 10 3 1 20 4 1 30 5 1 30 00 32 8 6 1 30 7 1 41 8 1 42 2 3 4 5 6 LED 7 LCD 8 13 08 9 E type G t...

Page 71: ...1 00 08 00 10 0 0 1 1 00 00 11 PID 0 PID 0 1 PID 0Hz 00 12 0 1 109 0 100 0 00 13 0 0 109 0 0 0 00 14 1 0 1 6000 0 1 00 15 1 0 1 6000 0 1 00 16 2 0 1 6000 0 1 00 17 2 0 1 6000 0 1 00 18 0 00 599 00 6 0...

Page 72: ...1 2 200V 0 0 255 0 0 0 8 400V 0 0 510 0 01 06 1 1 0 0 599 0 3 0 01 07 1 1 200V 0 0 255 0 8 400V 0 0 510 0 01 08 1 0 0 599 0 VF 1 5 VF P G 1 5 SLV 0 6 SV 0 1 PMSV 0 1 PMSL V 9 0 SLV2 1 0 01 09 1 200V 0...

Page 73: ...16 02 18 02 19 1 200V 50 240 400V 100 480 02 20 2 0 01 600 00 02 21 2 10 200 02 22 2 0 60000 02 23 2 200V 50 0 240 0 8 400V 100 0 480 0 02 24 2 0 01 600 00 02 25 2 4 8 599 0 50 0 60 0 8 02 26 2 2 16 4...

Page 74: ...S1 A xxx1b S1 B 0000 b xx0xb S2 A xx1xb S2 B x0xxb S3 A x1xxb S3 B 0xxxb S4 A 1xxxb S4 B 03 10 S5 S8 xxx0b S5 A xxx1b S5 B 0000 b xx0xb S6 A xx1xb S6 B x0xxb S7 A 03 x1xxb S7 B 0xxxb S8 A 1xxxb S8 B...

Page 75: ...3 12 0 03 03 29 DO1 DOG DO2 DOG xxx0b 1A xxx1b 1B 0000 b xx0xb 2A xx1xb 2B 10 03 30 0 0 1 PWM 03 31 03 30 03 30 0 50 32000Hz 03 30 1 10 1000Hz 1000 1 03 32 0 0 1000 0 100 1 03 33 100 0 100 0 0 0 1 03...

Page 76: ...000 0 100 0 1 04 08 AI2 100 0 100 0 0 1 04 09 I O AI 0 AI3 0 10V 0 10 1 AI3 10 10V 2 AI3 4 20mA 04 10 AI3 04 05 10 10 04 04 11 AO1 0 0 1 2 3 4 5 6 7 8 AI1 9 AI2 10 11 q 12 d 13 14 15 ASR 16 17 q 18 d...

Page 77: ...0 10 0 05 20 1 0 1 6000 0 10 0 05 21 2 0 1 6000 0 10 0 05 22 2 0 1 6000 0 10 0 05 23 3 0 1 6000 0 10 0 05 24 3 0 1 6000 0 10 0 05 05 25 4 0 1 6000 0 10 0 05 26 4 0 1 6000 0 10 0 05 27 5 0 1 6000 0 10...

Page 78: ...0 5 00 1 06 14 14 0 00 599 00 5 00 1 06 15 15 0 00 599 00 5 00 1 06 16 0 0 0 6000 0 0 0 1 06 17 1 0 0 6000 0 0 0 1 06 18 2 0 0 6000 0 0 0 1 06 19 3 0 0 6000 0 0 0 1 06 20 4 0 0 6000 0 0 0 1 06 21 5 0...

Page 79: ...100 00 0 50 07 09 0 0 1 2 3 07 07 10 07 12 07 13 200V 150 300 190 400V 250 600 380 07 14 0 00 10 00 2 00 07 15 50 200 100 07 16 0 00 100 00 0 00 07 17 07 18 0 1 5 0 07 19 0 100 50 07 20 0 100 20 07 21...

Page 80: ...0xxb x1xxb 0xxxb 1xxxb 08 01 20 200 HD 150 ND 120 08 02 200V 330V 410V 385V 400V 660V 820V 770V 08 03 30 200 HD 160 ND 120 08 04 08 05 OL1 xxx0b 0001b xxx1b 08 xx0xb xx1xb x0xxb x1xxb 0xxxb 1xxxb 08 0...

Page 81: ...08 48 0 0 4 1 08 49 0 0 4 1 08 50 XXX0B S6 A XXX1B S6 B 0000b 4 08 51 0 0 4 1 PID 2 AI2 08 52 0 100 00 100 00 4 08 53 PID 0 100 0 4 08 08 54 PID 0 10 0 1 0 4 08 55 PID 0 1 4 1 08 52 2 1 01 02 08 56 AI...

Page 82: ...10 10 PID 0 00 10 00 0 00 1 10 11 PID 0 0 1 2 10 12 PID 0 100 0 10 13 PID 0 0 10 0 1 0 10 PID 10 14 PID 0 0 100 0 100 0 1 10 15 PID 0 2 0 2 10 16 PID 0 100 0 2 10 17 PID 0 00 599 00 0 00 10 18 PID 0 0...

Page 83: ...20 11 08 1 0 0 599 0 0 0 11 09 2 0 0 599 0 0 0 11 10 3 0 0 599 0 0 0 11 11 0 0 25 5 1 0 11 12 0 100 80 11 13 0 120 60 1 11 11 14 11 17 11 18 0 0 599 0 0 00 11 19 0 0 1 11 20 0 200 140 11 21 0 100 100...

Page 84: ...400V 370 400V 400V 800V 740 11 66 6 00 60 00 20 2 11 67 2 0 12000 0 2 11 68 2 6 00 60 00 20 2 11 69 0 00 200 00 5 00 1 11 11 70 0 01 100 00 5 00 1 11 71 0 30000 100 1 11 72 1 0 01 300 00 30 00 1 11 73...

Page 85: ...0 0 Output Terminal DO1 Output Terminal R2 Output Terminal R1 0 Output Terminal PLC 12 06 12 10 12 11 12 12 12 13 12 14 12 15 12 16 LED 12 17 12 18 12 19 12 12 20 Vdc 12 21 kw 12 22 rpm VF SLV x 120 P...

Page 86: ...e d 1 D u rin gs p e e da g re e 1 D u rin gfa u ltd e te c tio n m in o rfa u lt 1 D u rin gfa u ltd e te c tio n m a jo rfa u lt R e s e rv e d 12 44 12 45 12 46 12 47 12 48 12 49 12 12 50 DI DO DI...

Page 87: ...3 08 0 2 2 60Hz 220 440V 3 3 60Hz 220 440V 4 2 50Hz 230 415V 5 3 50Hz 230 415V 6 2 50Hz 200 380V 7 3 50Hz 200 380V 8 PLC 9 2 60Hz 13 230 460V 10 3 60Hz 230 460V 11 2 60Hz 230 400V 12 3 60Hz 230 400V 1...

Page 88: ...2 7 0 9999 0 6 14 14 T8 1 0 9999 0 6 14 15 T8 2 7 0 9999 0 6 14 16 C1 0 65534 4 0 6 14 17 C2 0 65534 4 0 6 14 18 C3 0 65534 4 0 6 14 19 C4 0 65534 4 0 6 14 20 C5 0 65534 4 0 6 14 21 C6 0 65534 4 0 6...

Page 89: ...2 7 0 9999 0 15 14 T8 1 0 9999 0 15 15 T8 2 7 0 9999 0 15 16 C1 0 65534 4 0 15 17 C2 0 65534 4 0 15 18 C3 0 65534 4 0 15 19 C4 0 65534 4 0 15 20 C5 0 65534 4 0 15 21 C6 0 65534 4 0 15 22 C7 0 65534 4...

Page 90: ...01 01 8 16 12RTC 00 00 23 59 00 00 8 16 LCD 16 13RTC 0 1 2 DI 0 8 16 14P1 00 00 23 59 08 00 8 16 15P1 00 00 23 59 18 00 8 16 16P1 1 2 3 4 5 6 7 1 8 16 17P1 5 8 16 18P2 00 00 23 59 08 00 8 16 19P2 00...

Page 91: ...4 8 16 35 4 8 8 16 36RTC 0 0 8 1 1 2 2 3 3 4 4 5 1 2 16 37 RTC xxx0b RTC Run1 0000b 8 xxx1b RTC Run1 xx0xb RTC Run2 xx1xb RTC Run2 x0xxb RTC Run3 x1xxb RTC Run3 0xxxb RTC Run4 1xxxb RTC Run4 16 LCD 17...

Page 92: ...20 04 ASR 0 300 200 20 05 ASR 0 1 10 0 5 0 20 06 ASR 0 1 10 0 1 0 20 07 P PI 0 PI P 0 1 PI 20 08 ASR 0 000 0 500 0 004 20 20 09 1 0 00 2 55 0 61 1 20 10 1 0 01 10 00 0 05 1 20 11 2 0 00 2 55 0 61 1 20...

Page 93: ...9999 0 21 20 5 9999 9999 0 21 21 5 9999 9999 0 21 22 6 9999 9999 0 21 23 6 9999 9999 0 21 21 24 7 9999 9999 0 21 25 7 9999 9999 0 21 26 8 9999 9999 0 21 27 8 9999 9999 0 21 28 9 9999 9999 0 21 29 9 9...

Page 94: ...20 90 22 19 22 20 0 360 0 4 22 21 PM 0 PM 0 1 PMSLV 2 PMSV 3 22 22 PM 0 0 4 1 2 PG option card 3 4 5 6 7 8 9 22 PM 10 11 22 23 22 24 22 25 0 2 7 1 1 2 2 22 26 PMSLV 0 1 2 0 22 27 2 5 120 7 22 25 2 22...

Page 95: ...39 0 20 00 0 10 22 40 0 01 1 00 0 01 22 41 PM 0 22 11 1 22 11 0 22 42 Ka 64 8192 100 22 43 Kb 64 8192 2000 22 44 1 256 4 22 45 0 01 10 00 0 70 4 4 1 4 2 4 1 1 03 00 03 07 17 ON 2 Reset 3 12 4 1 LED O...

Page 96: ...ASR 21 PGO PG PG PG PG DEV PG 20 23 20 24 CE FB PID PID PID STO F1 F2 H C SF1 SF2 SG E G 58 STO2 SS1 58 EF0 0 0x2501 bit 2 EF1 S1 LED EF2 S2 EF3 S3 EF4 S4 EF5 S5 EF6 S6 EF7 S7 EF8 S8 CF07 Rotational...

Page 97: ...39 LED PF TOL 4 3 4 2 4 2 LED HPErr 13 00 OV UV MC OH1 OH2 LED OT 08 15 08 16 UT 08 19 08 20 bb1 bb2 bb3 bb4 bb5 bb6 bb7 bb8...

Page 98: ...0 LED DEV PG 20 23 20 24 20 28 OL1 V F V F OL2 CE CLA A CLB B Retry ES OS 20 20 20 21 ASR 20 PGO PG PG PG LED EF1 S1 EF2 S2 EF3 S3 EF4 S4 EF5 S5 EF6 S6 EF7 S7 EF8 S8 EF9 FB PID PID PID USP 03 00 03 07...

Page 99: ...V f V F SE05 PID 10 00 10 01 10 29 10 25 10 29 10 03 SE07 PG 1 PG 2 PM 22 08 SE08 PM SE09 PI PI 03 30 PID 10 00 10 01 07 05 FIRE ADC LED EEPROM DI 00 05 05 01 0 1 2 17 07 PG 3 20 27 PG 20 28 PG 11 00...

Page 100: ...17 00 17 09 02 R1 17 00 17 09 03 04 R2 05 Lm 07 Deadtime 06 02 01 02 21 08 00 14 09 4 5 PM PM IPErr PM 22 18 4 4 4 4 PM 01 22 02 02 PG option card PM PG card 03 04 05 06 PG card 07 08 PG card A B 09...

Page 101: ...0MCM 2 M12 R250 12 Nichifu NOP 700 NOH300K TIC 250 4001 2 14 3 5 12 5 3 10 M4 R2 4 R3 5 4 R5 5 4 Nichifu NH 1 9 TIC 2 3 5 5 5 4002 2 14 3 5 12 5 3 10 M4 R2 4 R3 5 4 R5 5 4 Nichifu NH 1 9 TIC 2 3 5 5 5...

Page 102: ...3 0 M10 R80 10 Nichifu NOP 60 150HA TIC 80 6215 152 300MCM M10 R150 10 Nichifu NOP 700 NOH300K TIC 150 6250 152 300MCM M10 R150 10 Nichifu NOP 700 NOH300K TIC 150 6270 152 300MCM M10 R150 10 Nichifu...

Page 103: ...A 3 Type 1 During installation all conduit hole plugs shall be removed and all conduit holes shall be used 690V 80A...

Page 104: ...to be used Inverter Short Circuit Rating This inverter has undergone the UL short circuit test which certifies that during a short circuit in the power supply the current flow will not rise above val...

Page 105: ...ircuit principal doit tre correctement c bl e Pour les terminaux monophas s d approvisionnement de l utilisation des intrants R L1 T L3 et de trois bornes d entr e de l utilisation de l offre de phase...

Page 106: ...rie avec le variateur et le moteur Ne branchez pas un facteur condensateur de correction de puissance ou suppresseur de tension la sortie du variateur S assurer que l interf rence g n r e par l entra...

Page 107: ...fonction de freinage d entra nement pour un maintien m canique sous peine de blessure Ne pas contr ler les signaux sur les circuits pendant que le lecteur est en marche 1 6 Entretien Inspection et re...

Page 108: ...BDE X O O O O O O O X O O O O O O O O O X O O O O O O O O O O O O O O O O O X O O O O O O O O O O O SJ T 11364 O GB T 26572 X GB T 26572 1000ppm RoHS 7 a 85 7 c I 100ppm RoHS 8 b 1000ppm RoHS 6 a 0 35...

Page 109: ...V f V f PG SLV SLV2 SV PMSV PMSLV Nominal current Please refer to the table below Nominal apparent power Please refer to the table below Maximum operating temperature 40 for IP20 50 for IP00 or top an...

Page 110: ...1881 95 7 3457 96 0 2037 97 4 3827 97 5 3934 97 7 8 A510 4215 S 3H 380 330 160 251 56 50 0 0 50 0 0 144 0 0 1474 94 4 2085 95 8 3780 96 1 2259 97 4 4194 97 6 4313 97 7 8 A510 4270 S 3 380 380 200 290...

Page 111: ......