Cod.Doc.2550041-REV 2.2.0 gb.doc
Pagina 22
A8
Generator maximum voltage
0000 / 0001
0001 = yes
A8.01
Stop without cooling
0000 / 0001
0000 = no
A8.02
Stop with cooling
0000 / 0001
0001 = yes
A8.03 Siren
relay
0000 / 0001
0001 = yes
A8.04
Alarm relay (if enabled)
0000 / 0001
0001 = yes
A8.05 Not
used
0000 / 0001
0000 = no
A9
Fuel
0000 / 0001
0001 = yes
A9.01
Stop without cooling
0000 / 0001
0000 = no
A9.02
Stop with cooling
0000 / 0001
0000 = no
A9.03 Siren
relay
0000 / 0001
0001 = yes
A9.04
Alarm relay (if enabled)
0000 / 0001
0001 = yes
A9.05 Not
used
0000 / 0001
0000 = no
A10
Maximum current
0000 / 0001
0001 = yes
A10.01
Stop without cooling
0000 / 0001
0000 = no
A10.02
Stop with cooling
0000 / 0001
0001 = yes
A10.03 Siren
relay
0000 / 0001
0001 = yes
A10.04
Alarm relay (if enabled)
0000 / 0001
0001 = yes
A10.05 Not
used
0000 / 0001
0000 = no
A11
Battery minimum voltage
0000 / 0001
0001 = yes
A11.01
Stop without cooling
0000 / 0001
0000 = no
A11.02
Stop with cooling
0000 / 0001
0000 = no
A11.03 Siren
relay
0000 / 0001
0001 = yes
A11.04
Alarm relay (if enabled)
0000 / 0001
0001 = yes
A11.05 Not
used
0000 / 0001
0000 = no
A12
Battery maximum voltage
0000 / 0001
0001 = yes
A12.01
Stop without cooling
0000 / 0001
0000 = no
A12.02
Stop with cooling
0000 / 0001
0001 = yes
A12.03 Siren
relay
0000 / 0001
0001 = yes
A12.04
Alarm relay (if enabled)
0000 / 0001
0001 = yes
A12.05 Not
used
0000 / 0001
0000 = no
A13
Starting failure
0000 / 0001
0001 = yes
A13.01
Stop without cooling (not influential, always as set to “no”)
0000 / 0001
0000 = no
A13.02
Stop with cooling (not influential, always as set to “no”)
0000 / 0001
0000 = no
A13.03 Siren
relay
0000 / 0001
0001 = yes
A13.04
Alarm relay (if enabled)
0000 / 0001
0001 = yes
A13.05 Not
used
0000 / 0001
0000 = no
E1
Remote stop
0000 / 0001
0001 = yes
E1.01
Stop without cooling (not influential, always as set to “yes”)
0000 / 0001
0001 = yes
E1.02
Stop with cooling (not influential, always as set to “no”)
0000 / 0001
0000 = no
E1.03 Siren
relay
0000 / 0001
0001 = yes
E1.04
Alarm relay (if enabled)
0000 / 0001
0001 = yes
E1.05 Not
used
0000 / 0001
0000 = no
E2
Emergency stop (not influential, always as set to “yes”)
0000 / 0001
0001 = yes
E2.01
Stop without cooling (not influential, always as set to “yes”)
0000 / 0001
0001 = yes
E2.02
Stop with cooling (not influential, always as set to “no”)
0000 / 0001
0000 = no
E2.03 Siren
relay
0000 / 0001
0001 = yes
E2.04
Alarm relay (if enabled)
0000 / 0001
0001 = yes
E2.05 Not
used
0000 / 0001
0000 = no
Summary of Contents for AT206
Page 1: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 1 ELECTRICAL PANEL AT206 AT206B USER MANUAL ...
Page 15: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 15 4 2 AT206 panel electrical drawing ...
Page 16: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 16 4 3 AT206B panel electrical drawing ...
Page 17: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 17 4 4 Diesel engine auxiliary connection ...
Page 18: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 18 4 5 Gasoline engine auxiliary connection ...