Cod.Doc.2550041-REV 2.2.0 gb.doc
Pagina 20
5.4 - Advanced menu parameters
Setup Description
Range
Default
Group 1
Panel nominal data
P1.01
Nominal frequence
50Hz= 0 60Hz=1
0
.02
Current Trasformer ratio (CT 100/5 = 20)
1…2000
20
.03
System (220V monophase, 220V triphase, 380V triphase)
0
=230M
1
=230T
2
=400T 0
Group 2
Engine start-up
P2.01
500 rpm signal from alternator or gen. (started engine)
0= from alternator Vac
1= permanent magnet alt. (saprisa)
2= pre-excited alternator (D+)
0
.02
Started engine alternator batterycharger voltage threshold
3-30V
10
.03
Started engine generator voltage threshold
20-500V
50
.04
Starting with power failure
On=1 Off=0
1
.05
Preheating time
1-60 sec
7
.06
Number of starting attempts
1-10
6
.07
Duration of starting attempts
1-30sec
5
.08
Pause time within starting attempts
1-20sec
10
.09
Automatic test enabling with remote stop signal presence
0= start not enable
1= start enable
1
.10
Alarm enabling delay at starting (oil/V/freq.)
1-60sec
8
.11
Air time
0-240 sec
5
.12
Air switch-off threshold
30-255V
100
Group 3
Motor stop
P3.01
Stop times (electromagnet closing time / gasoline engine stop time)
1-30sec
10
.02
Decelerated funct. time
1-60 sec
30
.03
Cooling time
1 – 300sec
120
Group 4
Protections
P4.01
Minimum frequency (fixed delay 5sec)
80 – 100 %
90%
.02
Maximum frequency (overspeed)
100 – 120%
110%
.03
Maximum frequency al. tripping delay
0-15 sec
2 sec
.04
Battery minimum frequency
7-12V
9
.05
Battery maximum frequency
13 – 17V
17V
.06
Load maximum current
10 – 2550A
100A
.07
Maximum current delay
0 – 600sec
10
.08
Tripping delay of “500rpm failure” (strap breaking)
0 –10 sec
5
.09
“Mechanical failure” tripping delay
0 - 10 sec
5
Group 5
Various
Range
Default
P5.01
Generator and network contactor closing delay
0,1 –5 sec
1
P5.02
Remote start input function
0= normal 1= ejp/t
0
P5.03
Re-commutation lock on network in case of alarm during EJP/T
1 = on
0 = off
0
P5.04
Hourcounter value
0 – 999.999
0
Group 6
Programmable outputs
P6.01
Programmable relay (terminal 63)
0= choke / air
1= glow plugs
2= alarm
3= fuel electrovalve
1= glow plugs
P6.02
Programmable relay (terminal 53 - 54)
0= alarm
1= decelerator
2= electromagnet or gasoline stop
0= alarm
P6.03
Programmable relay (terminal 62)
0= siren
1= alarm
0= siren
Note : Range P7.01, P7.02, P8.01 E P8.02 must always set in reference to 230V also if P1.03 =1 or P1.03=2
Summary of Contents for AT206
Page 1: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 1 ELECTRICAL PANEL AT206 AT206B USER MANUAL ...
Page 15: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 15 4 2 AT206 panel electrical drawing ...
Page 16: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 16 4 3 AT206B panel electrical drawing ...
Page 17: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 17 4 4 Diesel engine auxiliary connection ...
Page 18: ...Cod Doc 2550041 REV 2 2 0 gb doc Pagina 18 4 5 Gasoline engine auxiliary connection ...