„ active ”
- in this mode
{EXT. BARRIER}
input signal is transferred to
{BARRIER}
process
{EXT. BARRIER}
input signal.
Activation of
{EXT. BARRIER}
input (open
contact) causes door opening immediately – regardless of
{OPEN INP.}
and
{CLOSE INP.}
input signals.
CAUTION!
The door controller retries closing door attempts when the optical
barrier signal
{EXT. BARRIER}
disappears. Optical barrier state testing and
closing retries every 3 seconds. The door controller tries to close the door 5
times. If all 5 tries are unsuccessful, controller tries once more moving the door
with minimal speed and ignoring optical barrier signals. During this operation
however the possibility of mechanical obstruction is being checked.
8.
Access setup
8.1. Access pass.
(Access password), range: 000000 ÷ 999999
Setting the password to 000000 allows free access to the menu. Once any other
password is selected and stored it will be asked each time the menu is started.
There is no way to recover a lost password by the user or installer. In such
event please contact TechWind for assistance
9.
Region
9.1.
Language
, options: [ Polish, English ]
Language of the controller menu content.
is only capable of simultaneously having two language versions of the
menu. The default languages for the Polish market version are Polish and
English. Please contact TechWind about other language versions
A. Default set.
A.1. Restore
[ execute ]
„
Restore”
command allows to return all settings to their factory defaults. The description
of the factory default settings is included in the menu described in this manual.
CAUTION!
Restoring all values to the factory defaults will overwrite all settings
including any door/drive parameters. All initialisation and calibration procedures
have to be repeated as described in
chapter.
25