Working modes
4.1. Driver mode
, options: [ RS-485 lines / external inputs / automatic / manual ]
controller is designed as a universal unit to be used with various 3
rd
party
elevator control systems. To provide proper connection to different types of main controllers,
correct menu option must be chosen:
„ RS-485 lines ”
- systems control using RS-485 communication bus and
ModBus RTU protocol. It is required to provide proper data
transmission format and registers addresses.
„
external inputs
”
- systems control using separate
{CLOSE INP.}
and
{OPEN INP.}
inputs.
„ automatic ”
- automatic closing and opening option is used for service
purposes only. It allows for automatic opening and closing
door. Once it is selected doors are opening and closing every
5 second ignoring any external signals.
„ manual ”
- after setting this option and leaving the menu, each
[ENTER]
pressing will close and open doors alternately.
4.2. Door number
, range: 0
÷
3
Used in multi-door installation. It corresponds to the address of the
and is used in systems driven by RS-485 interface
ONLY
.
5.
Inputs
5.1 OPENING inp.
(OPENING input), options: [ inactive / active ]
Voltage controlled input. Receives signals from the main elevator controller. If
{OPEN INP.}
input is set to 'active', then signal on this input will open the door. If
{CLOSE INP.}
input (see
“
CLOSING inp.”
parameter description) is set to 'inactive', then
removing the signal will close the door.
5.2 CLOSING inp.
(CLOSING input), options: [ inactive / active ]
Voltage controlled input. Receives signals from the main elevator controller. If
{CLOSE INP.}
input is set to 'active', then signal on this input will close the door. If
{OPEN INP.}
input (see
“
OPENING inp.”
parameter description) is set to 'inactive', then
removing the signal will open the door.
It is not advisable to set
{OPEN INP.}
to inactive and
{CLOSE INP.}
to active.
Such settings may cause malfunction of the door if electrical wiring of these
inputs becomes damaged.
23