TechWind SDK-500 User Manual Download Page 1

USER'S MANUAL

elevator door controller 

  type: 

SDK-500

firmware version: 

1.21.0

Read the user's manual carefully before starting to use the unit. 

TechWind company reserves the right to introduce changes without prior notice.

  2013.03.12

   

                                        

                    

  

V.1.07  

Summary of Contents for SDK-500

Page 1: ...ator door controller type SDK 500 firmware version 1 21 0 Read the user s manual carefully before starting to use the unit TechWind company reserves the right to introduce changes without prior notice...

Page 2: ...demarks of the manufacturers or vendors of the respective products Software license agreement Software and firmware supplied with products is proprietary and furnished under license and can be used or...

Page 3: ...485 INTERFACE 14 3 12 EMERGENCY BATTERY POWER SUPPLY BUTTON 14 4 CONTROLLER PROGRAMMING 15 4 1 PROGRAMMING MENU 15 4 2 EDITING PARAMETERS 16 4 2 1 Numeric parameters 16 4 2 2 Switch parameters 16 4 3...

Page 4: ...f this device proper transport storage and assembly as well proper operation and professional maintenance is required TechWind disclaims responsibility for property damage or personal injuries resulti...

Page 5: ...ing force and reverse force Incorrect settings too high of current value corresponding to tightening force may cause damage to the motor SDK 500 menu allows for setting of the current corresponding to...

Page 6: ...ctly required to provide good grounding of controller metal housing and transformer cover using separate grounding wire to appropriate grounding terminal Motor and encoder wires must be shielded and f...

Page 7: ...2 3 1 1 2 3 4 5 1 2 3 4 1 2 3 4 5 1 2 ENCODER 24V AC 24V AC 0V 24V DC BATTERY AC POWER SUPPLY 0V SIGNAL B SIGNAL A 5V ENCODER MOTOR2 MOTOR1 EKRAN MOTOR 0V B A 5V RS 485 OPEN INP CLOSE INP END SWITCH I...

Page 8: ...sible An automatic battery charger circuitry is a part of the controller board and is designed to charge battery with 200 mA current which is sufficient to keep the battery fully charged but will not...

Page 9: ...9 connector the encoder can be connected directly to the SDK 500 board s screw terminals as shown in figure 3 4B 3 6 CONTROL INPUTS The SDK 500 controller is equipped with two control inputs provided...

Page 10: ...s and the SDK 500 will behave as if only voltage was applied to CLOSE INP input Figures 3 6 A and B shows how to connect the control inputs in systems where only one output is used by the main elevato...

Page 11: ...indicate detection of an obstacle during the door movement It is activated both in case of the optical barrier interruption as wells as in case of a mechanical blocking of the door movement Note that...

Page 12: ...troller unit or from the external optical barrier power supply A B Fig 3 9 External optical barrier connection CAUTION With the barrier not interrupted the voltage must at all times be applied to the...

Page 13: ...LL input is enabled by default 3 10 OPTIONAL TERMINAL POSITION CONTACT DOOR OPEN Figure 3 11 shows the connection of the optional terminal position contact NO type contact connected to the END SWITCH...

Page 14: ...WER SUPPLY BUTTON RUN ON BATTERY button allows to switch on the emergency battery power supply The SDK 500 controller is equipped with the input for back up battery power supply connection It allows t...

Page 15: ...nu options Entering of the passwords is similar to the edition of numeric parameters After entering of last digit of the password first menu position will be displayed if the password is correct or Wr...

Page 16: ...on the list can be selected for the given parameter Options of switching parameter are selected using buttons Short pressing of ENTER displays confirmation question message Save changes Select the an...

Page 17: ...er mode Parameter edition MENU ESC MENU ESC 5 Inputs MENU ESC 5 3 INSTALL inp 5 2 CLOSING inp ENTER ENTER MENU ESC ENTER 5 1 OPENING inp Parameter edition MENU ESC 8 Access setup 4 2 Door number MENU...

Page 18: ...he door the controller will display Kinetic energy exceeded message and automatically adjust maximum speed such as to account for the new weight setting 2 Speeds 2 1 V Opening range 0 10 0 79 m s Requ...

Page 19: ...nnectors see figure 6 1 at page 29 After changing motor power supply connection Installation procedure must be start again During this movement terminal positions of the door will be identified and st...

Page 20: ...is moved away from the obstacle the controller will attempt to close open the door once again If the obstacle is still in the door s way the procedure will be repeated up to 5 times If the obstacle i...

Page 21: ...losed door is tighten continuously power supply of motor is always on by CLOSING input closed door is tighten only if voltage is provided to the CLOSE INP input Removal of the voltage from CLOSE INP i...

Page 22: ...dirt and mechanical factors will cause additional movement resistance which will influence the current value As the controller is monitoring current has a chance to detect and signal maintenance need...

Page 23: ...each ENTER pressing will close and open doors alternately 4 2 Door number range 0 3 Used in multi door installation It corresponds to the address of the SDK 500 controller and is used in systems driv...

Page 24: ...options inactive normal open normal closed The relay connected to the output is not controlled when this option is set to inactive If set to normal open the relay will be in the closed state after the...

Page 25: ...0 999999 Setting the password to 000000 allows free access to the menu Once any other password is selected and stored it will be asked each time the menu is started There is no way to recover a lost p...

Page 26: ...INP input state is low CLOSE INP input state is high 5 1 NORMAL OPERATION Following screens are available during the normal operation SCREEN 1 line1 line2 producer name door state information initiali...

Page 27: ...SCREEN 7 line1 line2 door closing current force in A door opening current force in A SCREEN 8 line1 line2 present temperature of the controller executable components in C permissible temperature of t...

Page 28: ...ayed In case your password is forgotten please contact TechWind to receive new one use password Once the one use password is entered the message Enter new password is displayed User must enter new pas...

Page 29: ...ters characterising the door and its drive See the Controller programming section at page 15 for details CAUTION Entering wrong parameters i e not corresponding to actual door and drive characteristic...

Page 30: ...start bit 8 data bits 1 or 2 stop bits no parity control baud rate 19200 bit sec protocol Modbus RTU device address 0x18 N where N means value of Door number parameter All device parameters are availa...

Page 31: ...No Parameters structure version hexadecimal 0x0201 No 0 1 One use password state 0x0202 No 0x18 0x1B Controller address interface SLAVE 0x0203 No 4 Baud rate 0x0204 No 0 1 Permission of registers writ...

Page 32: ...0 1 OPENING inp parameter in Inputs menu 0 inactive 1 active 0x021D No 0 1 CLOSING inp parameter in Inputs menu 0 inactive 1 active 0x021E No 0 1 OPEN switch parameter in Calibration menu 0 inactive 1...

Page 33: ...zone length 4 0 cm 21 3 A Lock speed Locking speed MIN 2 5 cm s 21 3 C Threshold Permissible percentage exceedance of the average current value of opening closing cycle 35 22 3 E Pause time Delay of...

Page 34: ...xternal devices 15V DC 10 max 100 mA stabilized Communication interface option RS 485 8N1 and 8N2 Modbus RTU not separated Baud rate 19200 bit sec Display LCD alphanumeric 2 x 16 characters backlit Da...

Page 35: ...User s manual for elevator door controller SDK 500 35...

Page 36: ...TechWind Sp z o o Miszewko D browa 6 PL 80 297 Banino k Gda ska Poland tel 48 58 684 86 19 20 fax 48 58 684 86 17 http www techwind pl e mail biuro techwind pl...

Reviews: