Proline Promass 300 EtherNet/IP
Commissioning
17
Configuring the Internet protocol of the computer
NOTICE
Risk of electric shock! Components carry dangerous voltages!
‣
Never open the measuring device while it is connected to the supply voltage.
‣
The information and safety instructions in the Operating Instructions pertaining to the
measuring device must always be observed → 4.
The IP address can be assigned to the measuring device in a variety of ways:
• Dynamic Host Configuration Protocol (DHCP), factory setting:
The IP address is automatically assigned to the measuring device by the automation
system (DHCP server).
• Hardware addressing:
The IP address is set via DIP switches .
• Software addressing:
The IP address is entered via the
IP address
• DIP switch for "Default IP address":
To establish the network connection via the service interface (CDI-RJ45): the fixed IP
address 192.168.1.212 is used .
The measuring device works with the Dynamic Host Configuration Protocol (DHCP), on
leaving the factory, i.e. the IP address of the measuring device is automatically assigned by
the automation system (DHCP server).
To establish a network connection via the service interface (CDI-RJ45): the "Default IP
address" DIP switch must be set to
ON
. The measuring device then has the fixed IP address:
192.168.1.212. This address can now be used to establish the network connection.
If the IP address of the measuring device is assigned via hardware or software
addressing and the IP address is known, the network connection can also be
established directly via the Ethernet network → 16.
1. Via DIP switch 2, activate the default IP address 192.168.1.212: .
2. Switch on the measuring device.
3. Connect to the computer using a cable → 8.
4. If a 2nd network card is not used, close all the applications on the notebook.
Applications requiring Internet or a network, such as e-mail, SAP applications,
Internet or Windows Explorer.
5. Close any open Internet browsers.
6. Configure the properties of the Internet protocol (TCP/IP) as defined in the table:
IP address
192.168.1.XXX; for XXX all numerical sequences except: 0, 212 and 255 → e.g.
192.168.1.213
Subnet mask
255.255.255.0
Default gateway
192.168.1.212 or leave cells empty
4.3.2
Via WLAN interface
Configuring the Internet protocol of the mobile terminal
NOTICE
If the WLAN connection is lost during the configuration, settings made may be lost.
‣
Make sure that the WLAN connection is not disconnected while configuring the device.