Commissioning
Proline Promass 300 EtherNet/IP
16
IP address
assigned or
specified via:
Determine IP address settings via parameters or DIP switches
Local display
(if available)
Operating tool e.g.
FieldCare, DeviceCare,
AMS Device Manager,
SIMATIC PDM
DIP switches in
electronics compartment
Dynamic Host
Configuration Protocol
(DHCP), factory setting
Hardware addressing of
the IP address via DIP
switches
Software addressing of
the IP address via the
IP
address
parameter
DIP switch for "Default
Ethernet Network
Settings", use the fixed IP
address: 192.168.1.212
Position of the DIP switches → 8
Using the local display or an operating tool
The
IP address
parameter can be used to determine the IP address via the local display or
via an operating tool e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM.
4.3
Connecting the computer to the measuring device
The measuring device can be connected to the computer via:
• Service interface (CDI-RJ45)
• WLAN interface
• Ethernet-based fieldbuses
4.3.1
Via service interface (CDI-RJ45)
Preparing the measuring device
1. Depending on the housing version:
Release the securing clamp or securing screw of the housing cover.
2. Depending on the housing version:
Unscrew or open the housing cover.
3. The location of the connection socket depends on the measuring device and the
communication protocol:
Connect the computer to the RJ45 connector via the standard Ethernet connecting