background image

GB

5

4.2 - HYDRAULIC CONNECTION

• Connect the water pipes to the corresponding connections. See Ø and position on page 3.
• Install the hydraulic filter (supplied) on the water intake. Connect it using 2 isolation valves (not supplied) for cleaning

purposes.

• Install a shut-off valve (not supplied) if a fill / drainage connection is used.

CAUTION:
This device is not fitted with an expansion tank or a safety valve

.

These elements must be incorporated into the installation’s hydraulic circuit.
For installation of an electric heating module, install this safety valve in direct connection with the module (without isolation
valve).

NOTE: 

"Water connection hose" accessories may be used (refer to the accessories paragraph).

4.3 - ELECTRICAL CONNECTION

4.3.1 - GENERAL:

• The acceptable voltage variation is: ± 10% during operation.
• The electrical connection conduits must be fixed.
• Use the cable clamps at the rear of the unit and route the wires under the electric panel, at the level of the terminal strips.
• Class 1 unit.
• The electrical installation must comply with the standards and regulations applicable where the unit is being installed (in

particular NF C 15-100 

IEC 364).

4.3.2 - POWER SUPPLY

• The power supply must come from an isolation and electric protection device (not supplied) in accordance with existing

regulations.

• The installation must be protected by a 

three-pole circuit-breaker

(not included). See ratings in the table below.

Note

The unit is designed to be connected to a power supply having a TT neutral regime (neutral to ground) or TN.S regime
(to neutral) as per NF C 15-100.

POWER SUPPLY CABLE

• Section 

: see table below.

• The sections are given as an indication only. They have to be verified and adapted, if necessary, according to the

installation conditions and the standards in force.

• Make the electrical connections to the terminal board as per the electrical diagrams.

CURRENTS AND CROSS-SECTIONS

CAUTION:
In the case of a three-phase power supply, prior to commissioning the unit, make sure that the phase rotation
order is correct. If the rotation order is not respected, the phase-sequence controller restricts the unit from
operating.
To fix this, simply invert the 2 phases.

4.3.3 - CONTROL BY EXTERNAL CONTACT

• The unit can be controlled remotely by connecting a good-quality, potential-free external contact (not supplied) (contact

closed = operation authorised, contact open = stand-by).

• The On / Stand-by signal is connected to terminals 1 and 2 of the PCB located in the switch box (remove the existing

bridge - see diagram).

• The wiring of this contact must not be routed near power cables in

order to avoid electromagnetic disturbances.

• Use shielded cable with twisted pair (shielding grounded on generator

side).

• Max. connection cable length: 100 m.
• Minimum wire size: 0.5 mm

2

.

PHT 13

PHT 16

400/3N/50

400/3N/50

Nominal current

A

6.7

8.6

Max. current

A

8.9

10.7

Starting current

A

69

70

Protection rating

A

12

16

Cross-section of power cable

5 G 2.5 mm

2

5 G 2.5 mm

2

1

2

4

3

PHT

On/Stand-by

(

k

) Jumper to be removed

(

k

)

Summary of Contents for PHT 13

Page 1: ...aldamento Fluido refrigerante R 407 C Bomba de calor de alta temperatura con equipamiento hidr ulico s lo calefacci n Fluido refrigerante R 407 C Hochtemperatur W rmepumpe mit Hydraulikmodul Nur Heize...

Page 2: ...humidity of the ambient air very quickly This can modify its lubricant properties and lead in time to the destruction of the compressor MAINTENANCE INSTRUCTIONS 1 Never add oil to the appliance the c...

Page 3: ...lation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not designed to be used by people including child...

Page 4: ...st not be directed towards surrounding windows vibrations and noise must not be transmitted to a nearby building avoid exposure to salty air or sulphuric gas the proximity of the extractor fan project...

Page 5: ...he table below Note The unit is designed to be connected to a power supply having a TT neutral regime neutral to ground or TN S regime to neutral as per NF C 15 100 POWER SUPPLY CABLE Section see tabl...

Page 6: ...f a safety delay is in progress It stays on when the compressor is operating The control probe SD1 is located on the water inlet in the factory The controller is connected on a printed circuit board o...

Page 7: ...paragraph 5 4 If the light flashes it means that the compressor is starting required but that a safety delay is in progress This light stays on when the compressor has started To stop the unit open t...

Page 8: ...s 1 and above are accessed Note 2 The normal display level 0 returns automatically after 5 minutes if no buttons are pressed Level 0 Normal display Level 1 Level 2 Level 3 Level 4 Temperature S1 Alarm...

Page 9: ...tions Go to the PSS section in the menu Briefly and simultaneously press buttons 1 and 2 The message appears Enter the password using buttons 1 and 2 and validate it by simultaneously pressing buttons...

Page 10: ...tor lamp 7 Note The ventilation can restart after defrosting is completed to prevent excessive pressure build up For special climatic conditions the factory set time counter value of 30 minutes can be...

Page 11: ...a time delay system in order to respect a maximum number of starts per hour 10 a minimum stop time Cycle inversion valve The valve is actuated during defrost cycles Control hysteresis See the operati...

Page 12: ...ssure 2 bar That there are no leaks That the machine is stable That the power cables are well fixed to their connection terminals Terminals that are poorly tightened may cause overheating and malfunct...

Page 13: ...nal exchangers casings and the cleaning and protection of condensate tanks Treating odours and the disinfection of room surfaces and volumes also contributes to the cleanliness of the air breathed by...

Page 14: ...n the spare parts list for replacing defective refrigeration components Pipes may only be replaced by copper tubing in compliance with standard NF EN 12735 1 Leak detection in the case of pressure tes...

Page 15: ...8 16 4 14 4 51 4 59 19 64 23 70 26 19 17 4 20 4 60 4 69 19 67 23 70 26 19 18 4 25 4 69 4 78 19 70 23 70 26 19 19 4 31 4 79 4 88 19 73 23 70 26 20 20 4 36 4 88 4 97 19 77 23 70 26 20 21 4 40 4 93 5 02...

Page 16: ...4 53 4 76 20 08 23 98 26 56 17 4 28 4 62 4 85 20 09 23 98 26 55 18 4 36 4 71 4 94 20 10 23 98 26 53 19 4 43 4 79 5 03 20 12 23 98 26 52 20 4 51 4 88 5 12 20 13 23 98 26 50 21 4 55 4 92 5 16 20 13 23...

Page 17: ...apacitor C11 M11 capacitor C3 Filter E1 High pressure switch E2 Low pressure switch EV1 Electrovalve J1 Water differential pressure switch KA1 Phase sequence controller KM2 Contactor compressor KM3 Ci...

Page 18: ...F GB D P I E...

Page 19: ...F GB D P I E...

Page 20: ...dificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verbessert und k nnen ohne Vorank ndigung abge ndert...

Reviews: