GB
4
3 - INSTALLATION
• Protection index of the unit: IP 24.
• Select the location for the unit on the basis of the following criteria:
- the unit must be installed outside,
- the unit must not be installed near the following:
. sources of heat,
. combustible materials,
. return / air intake of an adjacent building.
- it is necessary to make sure that the free space around the unit is
provided (see the minimum dimensions on the drawing opposite),
- installation must be simple and make maintenance work easy,
- the unit must be fixed on a hard base and must be protected from risks
of flooding,
- the unit must be raised approximately 100 mm above the ground to
facilitate the drainage of condensates from the tank and to prevent it from
being encased in ice, of if required to connect the drainage of
condensates (see below),
- use the anti-vibration mountings supplied, making sure that they are not
compressed too much when the fastening screws are tightened,
- due to disturbance which may be caused by the noise, the blown air must
not be directed towards surrounding windows,
- vibrations and noise must not be transmitted to a nearby building,
- avoid:
. exposure to salty air or sulphuric gas,
. the proximity of the extractor fan,
. projections of mud (next to a roadway or path, for example),
. areas where there is strong wind blowing against the unit's air
exhaust.
DRAINAGE OF CONDENSATES
- If necessary, use the accessory part supplied to connect the condensate
drainage tube.
- The base has 2 drainage holes (one on each side).
- For condensate drainage, place the splined elbow in one of the holes,
depending on the unit's inclination or the preferred side, and plug the
other hole with the plastic cover.
- In this case, the tank and the drain line must be protected against freezing risks.
4 - CONNECTIONS
4.1 - DISASSEMBLY
• To remove side panel
A
:
- remove the 3 retaining screws
B
,
- lower the panel
(1)
using the handle
C
,
- pull the lower part of the panel toward you
(2)
.
B
C
A
B
2
1
B
A (m)
*
PHT 13/16
0.25
* This dimension does not account for the
following cases:
- Installation of the hydraulic filter with
shut-off valves positioned behind the
unit: provide 0.30 m.
- Installation of a heater unit behind the
unit: provide 0.30 m.
Minimum space above the device: 0.70 m.
Summary of Contents for PHT 13
Page 18: ...F GB D P I E...
Page 19: ...F GB D P I E...