4

3 - INSTALLATION

• Protection index of the unit: IP 24.
• Select the location for the unit on the basis of the following criteria:

- the unit must be installed outside,
- the unit must not be installed near the following:

. sources of heat,
. combustible materials,
. return / air intake of an adjacent building.

- it is necessary to make sure that the free space around the unit is

provided (see the minimum dimensions on the drawing opposite),

- installation must be simple and make maintenance work easy,
- the unit must be fixed on a hard base and must be  protected from risks

of flooding,

- the unit must be raised approximately 100 mm above the ground to

facilitate the drainage of condensates from the tank and to prevent it from
being encased in ice, of if required to connect the drainage of
condensates (see below),

- use the anti-vibration mountings supplied, making sure that they are not

compressed too much when the fastening screws are tightened,

- due to disturbance which may be caused by the noise, the blown air must

not be directed towards surrounding windows,

- vibrations and noise must not be transmitted to a nearby building,
- avoid:

. exposure to salty air or sulphuric gas,
. the proximity of the extractor fan,
. projections of mud (next to a roadway or path, for example),
. areas where there is strong wind blowing against the unit's air

exhaust.

DRAINAGE OF CONDENSATES

- If necessary, use the accessory part supplied to connect the condensate

drainage tube.

- The base has 2 drainage holes (one on each side).
- For condensate drainage, place the splined elbow in one of the holes,

depending on the unit's inclination or the preferred side, and plug the
other hole with the plastic cover.

- In this case, the tank and the drain line must be protected against freezing risks.

4 - CONNECTIONS

4.1 - DISASSEMBLY

• To remove side panel 

A

:

- remove the 3 retaining screws 

B

,

- lower the panel 

(1)

using the handle 

C

,

- pull the lower part of the panel toward you 

(2)

.

B

C

A

B

2

1

B

A (m)

*

PHT 13/16

0.25

* This dimension does not account for the

following cases:

- Installation of the hydraulic filter with

shut-off valves positioned behind the
unit: provide 0.30 m.

- Installation of a heater unit behind the

unit: provide 0.30 m.

Minimum space above the device: 0.70 m.

Summary of Contents for PHT 13

Page 1: ...aldamento Fluido refrigerante R 407 C Bomba de calor de alta temperatura con equipamiento hidr ulico s lo calefacci n Fluido refrigerante R 407 C Hochtemperatur W rmepumpe mit Hydraulikmodul Nur Heize...

Page 2: ...humidity of the ambient air very quickly This can modify its lubricant properties and lead in time to the destruction of the compressor MAINTENANCE INSTRUCTIONS 1 Never add oil to the appliance the c...

Page 3: ...lation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not designed to be used by people including child...

Page 4: ...st not be directed towards surrounding windows vibrations and noise must not be transmitted to a nearby building avoid exposure to salty air or sulphuric gas the proximity of the extractor fan project...

Page 5: ...he table below Note The unit is designed to be connected to a power supply having a TT neutral regime neutral to ground or TN S regime to neutral as per NF C 15 100 POWER SUPPLY CABLE Section see tabl...

Page 6: ...f a safety delay is in progress It stays on when the compressor is operating The control probe SD1 is located on the water inlet in the factory The controller is connected on a printed circuit board o...

Page 7: ...paragraph 5 4 If the light flashes it means that the compressor is starting required but that a safety delay is in progress This light stays on when the compressor has started To stop the unit open t...

Page 8: ...s 1 and above are accessed Note 2 The normal display level 0 returns automatically after 5 minutes if no buttons are pressed Level 0 Normal display Level 1 Level 2 Level 3 Level 4 Temperature S1 Alarm...

Page 9: ...tions Go to the PSS section in the menu Briefly and simultaneously press buttons 1 and 2 The message appears Enter the password using buttons 1 and 2 and validate it by simultaneously pressing buttons...

Page 10: ...tor lamp 7 Note The ventilation can restart after defrosting is completed to prevent excessive pressure build up For special climatic conditions the factory set time counter value of 30 minutes can be...

Page 11: ...a time delay system in order to respect a maximum number of starts per hour 10 a minimum stop time Cycle inversion valve The valve is actuated during defrost cycles Control hysteresis See the operati...

Page 12: ...ssure 2 bar That there are no leaks That the machine is stable That the power cables are well fixed to their connection terminals Terminals that are poorly tightened may cause overheating and malfunct...

Page 13: ...nal exchangers casings and the cleaning and protection of condensate tanks Treating odours and the disinfection of room surfaces and volumes also contributes to the cleanliness of the air breathed by...

Page 14: ...n the spare parts list for replacing defective refrigeration components Pipes may only be replaced by copper tubing in compliance with standard NF EN 12735 1 Leak detection in the case of pressure tes...

Page 15: ...8 16 4 14 4 51 4 59 19 64 23 70 26 19 17 4 20 4 60 4 69 19 67 23 70 26 19 18 4 25 4 69 4 78 19 70 23 70 26 19 19 4 31 4 79 4 88 19 73 23 70 26 20 20 4 36 4 88 4 97 19 77 23 70 26 20 21 4 40 4 93 5 02...

Page 16: ...4 53 4 76 20 08 23 98 26 56 17 4 28 4 62 4 85 20 09 23 98 26 55 18 4 36 4 71 4 94 20 10 23 98 26 53 19 4 43 4 79 5 03 20 12 23 98 26 52 20 4 51 4 88 5 12 20 13 23 98 26 50 21 4 55 4 92 5 16 20 13 23...

Page 17: ...apacitor C11 M11 capacitor C3 Filter E1 High pressure switch E2 Low pressure switch EV1 Electrovalve J1 Water differential pressure switch KA1 Phase sequence controller KM2 Contactor compressor KM3 Ci...

Page 18: ...F GB D P I E...

Page 19: ...F GB D P I E...

Page 20: ...dificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verbessert und k nnen ohne Vorank ndigung abge ndert...

Reviews: