SUMMARY TABLE OF ALARMS

(*)  The insufficient heat exchange alarm is activated if the temperature difference between the water inlet and outlet (after the

compressor has been operating for a few minutes) is insufficient (coolant charging problem, three-phase compressor running
“backwards”, jammed switch-over valve, faulty temperature probe, problem on the equipment, etc.).

5.8 - SPECIAL OPERATING FEATURES

• Reduction of water volume:

- the controller uses a self-adapting algorithm that analyses the compressor's operating time and can indicate deviations

of the current set point (and the corresponding hysteresis) in case of too short operating times (in order to extend the
operating times),

- for special applications, in which case the dimensioning of the unit and the circuit are carefully designed, this function

can be deactivated. To do this, set the parameter 

C08

to 

0

in the "

CP

" section of the parameterization menu.

• Defrosting:

- if the temperature detected by probe 

SD3

drops below the frosting temperature (dependent of the outside temperature),

a time counter is activated. This counter records the operating time in icing conditions. This status is indicated by the
flashing frosting indicator lamp (

7

),

- after an accumulated operating time of 30 minutes, a defrosting operation is launched (inversion of the refrigerating cycle

and shut-down of the fan) until the temperature detected by probe 

SD3

rises above the end of frosting temperature

threshold. The defrosting phase is indicated by the (steady) illumination of indicator lamp (

7

).

Note: 

The ventilation can restart after defrosting is completed to prevent excessive pressure build-up.
For special climatic conditions, the factory-set time counter value of 30 minutes can be adjusted. To do this, modify
parameter 

d03

in the defrosting section "

dFr

".

• Evaporation pressure regulation:

-  the ECH controller is equipped with a variable voltage regulator for the

fan's power supply,

- based on temperature information (read by the 

SD3

probe located on

the evaporator), the controller varies the supply voltage of the electric
fan according to the diagram opposite.

Circulating pump control:

- the pump is actuated when the unit operating or in 

stand-by

mode,

- the pump is stopped when the unit is completely 

OFF

. The shut-down

of the pump is delayed 1 minute after the compressor stops. An anti-freeze device forces pump operation if the outside
temperature (probe 

SD4

) drops below 0°C,

- an "anti-sticking" device forces pump operation (if stopped) for 3 seconds every 24 hours.

Alarm

Code Inhibition delay

Compressor

stop

Fan stop

Circulating pump

shut-down

Remarks

Fault on probe 1

E40

X

X

Fault on probe 2

E06

X

X

Fault on probe 3

E07

X

X

Fault on probe 4

E42

X

X

Forced circulating
pump operation

H.P.

E01

X

B.P. (low pressure)

E02

30'' at start-up

X

X

From probe

SD2

 (water outlet).

Threshold : 4° C

10'' in operation

X

X

X

If passage

30'' at start-up

reset

manual

5 min at start-up

Manual reset.

+

Inactive in

5 min in operation

anti-freeze phase.

From probe

SD1

(water inlet).
Threshold: 70° C
adjustable (A25)

E41

X

X

E44

E05

60''

X

X

E45

X

X

X

E46

30''

X

Configuration error

Anti-freeze (water
heat exchanger)

Water flow rate

Insufficient heat
exchange  (*)

Max. water
temperature

Max. voltage (100%)

Min. voltage (60%)

Evaporation
temperature

Summary of Contents for PHT 13

Page 1: ...aldamento Fluido refrigerante R 407 C Bomba de calor de alta temperatura con equipamiento hidr ulico s lo calefacci n Fluido refrigerante R 407 C Hochtemperatur W rmepumpe mit Hydraulikmodul Nur Heize...

Page 2: ...humidity of the ambient air very quickly This can modify its lubricant properties and lead in time to the destruction of the compressor MAINTENANCE INSTRUCTIONS 1 Never add oil to the appliance the c...

Page 3: ...lation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not designed to be used by people including child...

Page 4: ...st not be directed towards surrounding windows vibrations and noise must not be transmitted to a nearby building avoid exposure to salty air or sulphuric gas the proximity of the extractor fan project...

Page 5: ...he table below Note The unit is designed to be connected to a power supply having a TT neutral regime neutral to ground or TN S regime to neutral as per NF C 15 100 POWER SUPPLY CABLE Section see tabl...

Page 6: ...f a safety delay is in progress It stays on when the compressor is operating The control probe SD1 is located on the water inlet in the factory The controller is connected on a printed circuit board o...

Page 7: ...paragraph 5 4 If the light flashes it means that the compressor is starting required but that a safety delay is in progress This light stays on when the compressor has started To stop the unit open t...

Page 8: ...s 1 and above are accessed Note 2 The normal display level 0 returns automatically after 5 minutes if no buttons are pressed Level 0 Normal display Level 1 Level 2 Level 3 Level 4 Temperature S1 Alarm...

Page 9: ...tions Go to the PSS section in the menu Briefly and simultaneously press buttons 1 and 2 The message appears Enter the password using buttons 1 and 2 and validate it by simultaneously pressing buttons...

Page 10: ...tor lamp 7 Note The ventilation can restart after defrosting is completed to prevent excessive pressure build up For special climatic conditions the factory set time counter value of 30 minutes can be...

Page 11: ...a time delay system in order to respect a maximum number of starts per hour 10 a minimum stop time Cycle inversion valve The valve is actuated during defrost cycles Control hysteresis See the operati...

Page 12: ...ssure 2 bar That there are no leaks That the machine is stable That the power cables are well fixed to their connection terminals Terminals that are poorly tightened may cause overheating and malfunct...

Page 13: ...nal exchangers casings and the cleaning and protection of condensate tanks Treating odours and the disinfection of room surfaces and volumes also contributes to the cleanliness of the air breathed by...

Page 14: ...n the spare parts list for replacing defective refrigeration components Pipes may only be replaced by copper tubing in compliance with standard NF EN 12735 1 Leak detection in the case of pressure tes...

Page 15: ...8 16 4 14 4 51 4 59 19 64 23 70 26 19 17 4 20 4 60 4 69 19 67 23 70 26 19 18 4 25 4 69 4 78 19 70 23 70 26 19 19 4 31 4 79 4 88 19 73 23 70 26 20 20 4 36 4 88 4 97 19 77 23 70 26 20 21 4 40 4 93 5 02...

Page 16: ...4 53 4 76 20 08 23 98 26 56 17 4 28 4 62 4 85 20 09 23 98 26 55 18 4 36 4 71 4 94 20 10 23 98 26 53 19 4 43 4 79 5 03 20 12 23 98 26 52 20 4 51 4 88 5 12 20 13 23 98 26 50 21 4 55 4 92 5 16 20 13 23...

Page 17: ...apacitor C11 M11 capacitor C3 Filter E1 High pressure switch E2 Low pressure switch EV1 Electrovalve J1 Water differential pressure switch KA1 Phase sequence controller KM2 Contactor compressor KM3 Ci...

Page 18: ...F GB D P I E...

Page 19: ...F GB D P I E...

Page 20: ...dificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verbessert und k nnen ohne Vorank ndigung abge ndert...

Reviews: