background image

GB

6

4.3.4 - REMOTE CONTROL

• See paragraph "accessories".

4.3.5 - MISCELLANEOUS

• Alarm transfer:

Potential-free changeover contact (2A - 250 VAC max.) available on the unit's terminal strip (terminals 5 (common), 6
and 7 of the printed circuit) for remote signaling. See schematic.

- In case of alarm:

- contact open between terminals 5 and 6,
- contact closed between terminals 5 and 7.

5 - OPERATION OF “ECH” ELECTRONIC CONTROL

• See the wiring diagrams at the back of the manual.

5.1 - DELIVERY STATE

• The control unit is supplied fitted in the machine and

factory pre-set.

• All the connections are made except those concerning the

available signals or the options.

5.2 - PRINCIPLE

• The microprocessor controls the operation of the machine

and of the associated alarms.
It continuously compares the water temperature
measured by the probe 

SD1

and the setpoint temperature

value entered via the keyboard.
Each operating request produced by the control unit is
indicated by the light (

6

) (see below).

This light flashes if a safety delay is in progress. It stays on when the compressor is operating.

• The 

control probe SD1

is located on the 

water inlet

in the factory.

• The controller is connected on a printed circuit board on which the inputs and outputs are connected. 

On this board: 

- 12 V supply transformer,
- the alarm report relay,
- the 230 V circuit fuse (4 A - 250 V - 5x20 - fast - breaking capacity: 1.5 kA).

5.3 - PRESENTATION

5.3.1

DISPLAY KEYBOARD

(1) 

Key for:

- Local On / Off control,
- access to parameters (in combination with button (

2

)),

- alarm clearance,
-  hour counter reset.

(2) 

Key for:

- access to parameters (in combination with button (

1

)).

(3)

LED display.

(4)

Cooling mode indicator (not used).

(5)

Heating mode indicator.

(6)

Compressor on indicator.

(7)

Defrosting indicator.

(8)

Anti-freeze on indicator.

(9)

Decimal point: if illuminated when the operating time is displayed, the value must be multiplied by 100.

6

4

2

7

8

3

9

1

5

DIGITAL INPUTS

12 VAC 

SUPPLY

TRANSFORMER

ACTUATORS

SD1     Water inlet

temperature probe

(for control)

SD2     Water

outlet temperature

probe

(for anti-

freeze protection)

SD3     Air heat

exchanger

temperature probe

(for defrosting and

pressure

adjustment)

SD4     Outside

temperature probe

ECH 210 BDT

CONTROLLER

AI1
AI2
AI3
AI4

Summary of Contents for PHT 13

Page 1: ...aldamento Fluido refrigerante R 407 C Bomba de calor de alta temperatura con equipamiento hidr ulico s lo calefacci n Fluido refrigerante R 407 C Hochtemperatur W rmepumpe mit Hydraulikmodul Nur Heize...

Page 2: ...humidity of the ambient air very quickly This can modify its lubricant properties and lead in time to the destruction of the compressor MAINTENANCE INSTRUCTIONS 1 Never add oil to the appliance the c...

Page 3: ...lation check that its power supply is disconnected and locked out 1 4 USE OF EQUIPMENT This device is designed for heating buildings This appliance is not designed to be used by people including child...

Page 4: ...st not be directed towards surrounding windows vibrations and noise must not be transmitted to a nearby building avoid exposure to salty air or sulphuric gas the proximity of the extractor fan project...

Page 5: ...he table below Note The unit is designed to be connected to a power supply having a TT neutral regime neutral to ground or TN S regime to neutral as per NF C 15 100 POWER SUPPLY CABLE Section see tabl...

Page 6: ...f a safety delay is in progress It stays on when the compressor is operating The control probe SD1 is located on the water inlet in the factory The controller is connected on a printed circuit board o...

Page 7: ...paragraph 5 4 If the light flashes it means that the compressor is starting required but that a safety delay is in progress This light stays on when the compressor has started To stop the unit open t...

Page 8: ...s 1 and above are accessed Note 2 The normal display level 0 returns automatically after 5 minutes if no buttons are pressed Level 0 Normal display Level 1 Level 2 Level 3 Level 4 Temperature S1 Alarm...

Page 9: ...tions Go to the PSS section in the menu Briefly and simultaneously press buttons 1 and 2 The message appears Enter the password using buttons 1 and 2 and validate it by simultaneously pressing buttons...

Page 10: ...tor lamp 7 Note The ventilation can restart after defrosting is completed to prevent excessive pressure build up For special climatic conditions the factory set time counter value of 30 minutes can be...

Page 11: ...a time delay system in order to respect a maximum number of starts per hour 10 a minimum stop time Cycle inversion valve The valve is actuated during defrost cycles Control hysteresis See the operati...

Page 12: ...ssure 2 bar That there are no leaks That the machine is stable That the power cables are well fixed to their connection terminals Terminals that are poorly tightened may cause overheating and malfunct...

Page 13: ...nal exchangers casings and the cleaning and protection of condensate tanks Treating odours and the disinfection of room surfaces and volumes also contributes to the cleanliness of the air breathed by...

Page 14: ...n the spare parts list for replacing defective refrigeration components Pipes may only be replaced by copper tubing in compliance with standard NF EN 12735 1 Leak detection in the case of pressure tes...

Page 15: ...8 16 4 14 4 51 4 59 19 64 23 70 26 19 17 4 20 4 60 4 69 19 67 23 70 26 19 18 4 25 4 69 4 78 19 70 23 70 26 19 19 4 31 4 79 4 88 19 73 23 70 26 20 20 4 36 4 88 4 97 19 77 23 70 26 20 21 4 40 4 93 5 02...

Page 16: ...4 53 4 76 20 08 23 98 26 56 17 4 28 4 62 4 85 20 09 23 98 26 55 18 4 36 4 71 4 94 20 10 23 98 26 53 19 4 43 4 79 5 03 20 12 23 98 26 52 20 4 51 4 88 5 12 20 13 23 98 26 50 21 4 55 4 92 5 16 20 13 23...

Page 17: ...apacitor C11 M11 capacitor C3 Filter E1 High pressure switch E2 Low pressure switch EV1 Electrovalve J1 Water differential pressure switch KA1 Phase sequence controller KM2 Contactor compressor KM3 Ci...

Page 18: ...F GB D P I E...

Page 19: ...F GB D P I E...

Page 20: ...dificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verbessert und k nnen ohne Vorank ndigung abge ndert...

Reviews: