34
Indoor Unit KPAV128R5TAA
Outdoor Unit GRV129R5VAA
COOLING
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at 230V ~ 50Hz
Rating Conditions Running Amps. A
0.29 0.32
5.6 6.2
Power Input kW
0.070
0.076 1.154 1.13
Full Load Conditions Running Amps. A
0.29 0.32 6.59 7.2
Power Input kW
0.070 0.076 1.374 1.52
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 – 240V ~ 50Hz
Rating Conditions Running Amps. A 0.29 0.32 5.6 6.2
Power Input kW 0.070 0.076 1.22 1.37
Full Load Conditions Running Amps. A 0.29 0.32 7.7 8.3
Power Input kW 0.070 0.076 1.68 1.83
Rating Conditions
: Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions : Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.