background image

TECDrive TEC-3 User Guide Revision 1.20 

28 

www.tecmotors.co.uk/tecdrive 

 

 

9

 

Te

ch

n

ical 

Da

ta

 

9.4.

 

Additional Information for UL Compliance 

TECDrive E3 is designed to meet the UL requirements. For an up to date list of UL compliant products, please refer to UL listing NMMS.E226333 
In order to ensure full compliance, the following must be fully observed. 
 

Input Power Supply Requirements 

Supply Voltage 

200 

 240 RMS Volts for 230 Volt rated units, + /- 10% variation allowed. 240 Volt RMS Maximum 

380 

 480 Volts for 400 Volt rated units, + / - 10% variation allowed, Maximum 500 Volts RMS 

Imbalance 

Maximum 3% voltage variation between phase 

 phase voltages allowed 

All TECDrive E3 units have phase imbalance monitoring. A phase imbalance of > 3% will result in the drive tripping.  
For input supplies which have supply imbalance greater than 3% (typically the Indian sub- continent & parts of Asia 
Pacific including China) Invertek Drives recommends the installation of input line reactors. 

Frequency 

50 

 60Hz + / - 5% Variation 

Short Circuit Capacity 

Voltage Rating 

Min kW (HP) 

Max kW (HP) 

Maximum supply short-circuit current 

115V 

0.37 (0.5) 

1.1 (1.5) 

100kA rms (AC) 

230V 

0.37 (0.5) 

11 (15) 

100kA rms (AC) 

400 / 460V 

0.75 (1) 

22 (30) 

100kA rms (AC) 

All the drives in the above table are suitable for use on a circuit capable of delivering not more than the above 
specified maximum short-circuit Amperes symmetrical with the specified maximum supply voltage when protected 
by Class J fuses. 

Mechanical Installation Requirements 

All TECDrive E3 units are intended for indoor installation within controlled environments which meet the condition limits shown in section 
9.1 
The drive can be operated within an ambient temperature range as stated in section 9.1 
For IP20 units, installation is required in a pollution degree 1 environment 
For IP66 (Nema 4X) units, installation in a pollution degree 2 environment is permissible 
Frame size 4 drives must be mounted in an enclosure in a manner that ensures the drive is protected from 12.7mm (1/2 inch) of deformation 
of the enclosure if the enclosure impacted. 

Electrical Installation Requirements 

Incoming power supply connection must be according to section 4.3 
Suitable Power and motor cables should be selected according to the data shown in section 9.2 and the National Electrical Code or other 
applicable local codes. 
Motor Cable 

75°C Copper must be used 

Power cable connections and tightening torques are shown in sections 3.3 and 3.5 
Integral Solid Sate short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in 
accordance with the national electrical code and any additional local codes. Ratings are shown in section 9.2 
Transient surge suppression must be installed on the line side of this equipment and shall be rated 480Volt (phase to ground), 480 Volt 
(phase to phase), suitable for over voltage category iii and shall provide protection for a rated impulse withstand voltage peak of 4kV. 
UL Listed ring terminals / lugs must be used for all bus bar and grounding connections 

General Requirements 

TECDrive E3 provides motor overload protection in accordance with the National Electrical Code (US).  

 

Where a motor thermistor is not fitted, or not utilised, Thermal Overload Memory Retention must be enabled by setting P-50 = 1 

 

Where a motor thermistor is fitted and connected to the drive, connection must be carried out according to the information shown 
in section 4.9.2 

9.5.

 

EMC Filter Disconnect 

Drives with an EMC filter have an inherently higher leakage current to Ground (Earth).  For applications where tripping occurs the EMC filter can 
be disconnected (on IP20 units only) by completely removing the EMC screw on the side of the product. 

Remove the screw as indicated below 

 

The TECDrive product range has input supply voltage surge suppression components fitted to protect the drive from line voltage transients, 
typically originating from lightning strikes or switching of high power equipment on the same supply. 
 
When carrying out a HiPot (Flash) test on an installation in which the drive is built, the voltage surge suppression components may cause the 
test to fail.  To accommodate this type of system HiPot test, the voltage surge suppression components can be disconnected by removing the 
VAR screw.  After completing the HiPot test, the screw should be replaced and the HiPot test repeated.  The test should then fail, indicating that 
the voltage surge suppression components are once again in circuit. 

 

 

Summary of Contents for TECDrive TEC -3-120070-101 Series

Page 1: ...uide Revision 1 20 www tecmotors co uk tecdrive 1 1 Quick Start Up TECDrive User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 22kW 0 5 30HP 110 480V Distributed by TEC Electric Motors www tecm...

Page 2: ...TECDrive TEC 3 User Guide Revision 1 20 2 www tecmotors co uk tecdrive 1 Quick Start Up Di and Operating Instructions...

Page 3: ...ions 14 4 9 Motor Thermal overload Protection 15 4 10 EMC Compliant Installation 15 4 11 Optional Brake Resistor 15 5 Operation 16 5 1 Managing the Keypad 16 5 2 Operating Displays 16 5 3 Changing Par...

Page 4: ...g from transport receipt of delivery installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installatio...

Page 5: ...normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the...

Page 6: ...before connecting the supply 9 5 EMC Filter Disconnect 28 7 Check the supply cable and motor cable for faults or short circuits 8 Route the cables 9 Check that the intended motor is suitable for use...

Page 7: ...to Stop Connect a potentiometer 5k 10k between terminals 5 6 and 7 as shown o Adjust the potentiometer to vary the speed from P 02 0Hz default to P 01 50 60 Hz default Quick Start IP66 Switched Switc...

Page 8: ...1 0 75 1 4 3 1 TEC 3 120070 1F1 TEC 3 120070 101 1 5 2 7 1 TEC 3 220070 1F4 TEC 3 220070 104 1 5 2 7 2 TEC 3 220105 1F4 TEC 3 220105 104 2 2 3 10 5 2 N A TEC 3 320153 104 4 0 5 15 3 3 200 240V 10 3Pha...

Page 9: ...e suitable for use in pollution degree 1 environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingres...

Page 10: ...section 9 1 The drive must be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should b...

Page 11: ...nduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On the...

Page 12: ...d must be connected to system ground Ground impedance must conform to the requirements of national and local industrial safety regulations and or electrical codes The integrity of all ground connectio...

Page 13: ...mended to be installed in the supply line for drives where any of the following conditions occur o The incoming supply impedance is low or the fault level short circuit current is high o The supply is...

Page 14: ...STOP Run in Hand 0 4 Run in Hand Speed controlled from the Local POT Run in Auto 0 Speed controlled using Analog input 2 e g from PLC with 4 20mA signal Run in Speed Control STOP Run in PI Control 5 1...

Page 15: ...ry Supply Cable Type Motor Cable Type Control Cables Maximum Permissible Motor Cable Length C16 Shielded1 Shielded1 5 Shielded4 1M 5M7 C2 Shielded2 Shielded1 5 5M 25M7 C3 Unshielded3 Shielded2 25M 100...

Page 16: ...nds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show Drive is enabled r...

Page 17: ...from the motor nameplate enables the slip compensation function and the TECDrive display will now show motor speed in RPM All speed related parameters such as Minimum and Maximum Speed Preset Speeds e...

Page 18: ...ncy 4 32 8 kHz Sets maximum effective switching frequency of the drive If rEd is displayed when the parameter is viewed the switching frequency has been reduced to the level in P00 32 due to excessive...

Page 19: ...Power On or Reset the drive will automatically start if Digital Input 1 is closed To Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The numbers of restart att...

Page 20: ...mmunication An suffix means that the drive will coast stop output immediately disabled but will not trip P 37 Access Code Definition 0 9999 101 Defines the access code which must be entered in P 14 to...

Page 21: ...3 Advanced Parameters Par Description Minimum Maximum Default Units P 51 Motor Control Mode 0 5 0 0 Vector speed control mode 1 V f mode 2 PM motor vector speed control 3 BLDC motor vector speed contr...

Page 22: ...cess data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C...

Page 23: ...T STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which must be Normally Closed When the input opens the drive trips show...

Page 24: ...ntrol Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 14 1 STOP ENABLE PI Speed Re...

Page 25: ...emperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance P Loss Input Phase Loss Trip SC trp Communications Loss Trip...

Page 26: ...gh Run Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoint 0 5000 Setpo...

Page 27: ...8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20...

Page 28: ...cording to section 4 3 Suitable Power and motor cables should be selected according to the data shown in section 9 2 and the National Electrical Code or other applicable local codes Motor Cable 75 C C...

Page 29: ...sed over 10 C in order to start the drive 10 Factory Default parameters loaded 11 External trip E trip requested on digital input 3 Normally closed contact has opened for some reason If motor thermist...

Reviews: