Technical manual of 

FanControl-U2 module

7

Menu

Menu 

code

Factory 

default

Note

Delay prior to climatic 

system activation

26

2

1 – 5 min; 2 – 10 min; 3 – 15 min; 4 — 20 min; 

5 — 25 min; 6 — 30 min 

Engine temperature to 

acitvate the climate 

system

28

2

1 — 30°C; 2 — 40°C; 3 — 50°C; 4 — 60°C; 

5 — 70°C; 6 — 80°C;

Output №14 adjustment

30

1

1 — Heater operation (status).

The  output  generates  a  constant  level  signal 

while a heater is running (If it is activated with 

FanControl);

2 — Control of recirculating pump.

The  output  generates  a  constant  level  signal 

while  the  engine  heater  is  running  and  also 

within 2 minutes after the heater is deactivated. 

The signal is formed if the heater is activated 

with FanControl.

3 — Interior ventilation running (status).

The  output  generates  a  constant  level  while 

the ventilation is running (If it is activated with 

FanControl).

4 — The ignition imitation. 

The output generates a pulse signal during 5 

sec.  The  output  stops  generating  the  signal 

earlier  if  the  FanControl  module  detects  that 

the ignition has been turned OFF or the heater 

has shutdown.

5 — Auxiliary air heaters control.

The  output  generates  a  constant  level  signal 

if the engine heater is turned ON. The output 

stops generating the signal if the engine heater 

is turned OFF. The output doesn’t generate any 

signal if the auxiliary heater mode is activated.

6  —  Cooling  system  loop-switching  valve 

control.

The  output  generates  a  constant  level  signal 

after the engine heater is turned ON. The output 

stops generating the signal in 20 minutes after 

the  engine  heater  has  been  turned  off.  If  the 

engine  has  been  started  before  20  minutes 

expire  –  the  signal  will  vanish  in  5  minutes. 

If  the  engine  has  been  shut  down  before  5 

minutes  expire  –  the  module  will  continue 

generating the signal for 20 minutes.

Output №15 adjustment

32

Engine heater automatic 

shutdown

44

2

1  —  After  the  driver’s  door  is  opened  or  the 

brake pedal is pressed.

2 — After the ignition is turned ON.

Used only in special cases. Check documentation to see which vehicles require these settings (www.tecel.ru/en/).

** 

Sensor is installed if there is no data in the CAN-bus.

Heater operation time

This option (table 3 option №10) allows to setup the module operation time (from 10 to 120 

min. with 10 min. intervals). Programming is performed with the programming button (vehicle's 

OEM button or the built-in one).

To be able to check or change the value of this option - switch the vehicle's ignition ON, no later 

than in 10 seconds after turning the ignition ON press the programming button 10 times, wait 

until the module indicates the option status by the corresponding number of LED flashes (from 1 

to 12). To change the time interval, enter a desired value by pressing the programming button the 

number of times required to advance from the current value to a desired one.

Summary of Contents for FanControl-U2

Page 1: ...www tecel ru FanControl U2 Technical manual...

Page 2: ...84 3 E90 X5 E70 X5 F15 X6 E71 6 63 64 X4 F26 X6 F16 X1 F48 7 G11 G12 5 G30 Mini Cooper 2014 Countryman F60 2017 Land Rover Range Rover Vogue 2013 Range Rover Vogue 2014 Range Rover Sport 2014 Discover...

Page 3: ...al data bus 4 Grey blue LIN 2 Serial data bus 5 Blue yellow Digital bus Special bus for controlling Webasto Thermo Top C Evo5 Eberspacher D5WS heaters Can be used for control of aftermarket heaters an...

Page 4: ...programming can also be carried out either with a programming button one of the vehicle s interior buttons the information on which button is used on a particular vehicle is available at www tecel ru...

Page 5: ...as no data entry module will leave programming mode Connection to CAN bus Connection types There are two types of module connection to CAN bus Parallel connection It is used to control factory heaters...

Page 6: ...Automatic identification 2 Webasto 3 Ebersp cher 4 Protocol control is forbidden 5 Factory Webasto heater alternative protocol for VAG 6 Factory Webasto heater for RR Evoque 2011 2013 7 Factory Ebersp...

Page 7: ...heater mode is activated 6 Cooling system loop switching valve control The output generates a constant level signal after the engine heater is turned ON The output stops generating the signal in 20 m...

Page 8: ...de OFF the default value W BUS Ebersp cher protocol selection In most cases the protocol is assigned automatically when you connect the system to a heater Manual selection of the protocol is required...

Page 9: ...ng Technical data and operating conditions Table 4 Package contents Name Value Supply voltage V 9 15 Maximum current draw in operating mode mA 200 Maximum current draw in standby mode mA 2 5 Temperatu...

Reviews: