135
10.3 Isolated Programming & Monitoring Connector
Refer to Table 10-1 for detailed description of the Rear Panel Isolated Programming & Monitoring
connector. To provide the lowest noise performance, it is recommended to use shielded-twisted
pair wiring.
Refer to Fig.10-1 for description of the connector.
Isolated programming plug P/N: MC1.5/8-ST-3.81, Phoenix.
Fig.10-1: Isolated Programming & Monitoring connector
Terminal
Signal name
Function
Range 0-5/0-10V
IS510 option
Range 4-20mA
IS420 option
1
SHLD
Shield, connected internally to chassis of
the supply.
Chassis ground
2
+VPROG_ISO Output voltage programming input
0-5/0-10V
4-20mA
3
+IPROG_ISO
Output current programming input
0-5/0-10V
4-20mA
4
GND
Ground for programming signals.
Ground
Ground
5
GND
Ground for programming signals.
Ground
Ground
6
+VMON_ISO
Output voltage monitoring output
0-5/0-10V
4-20mA
7
+IMON_ISO
Output current monitoring output
0-5/0-10V
4-20mA
8
SHLD
Shield, connected internally to chassis of
the supply.
Chassis ground
Table 10-1: Detailed description of the Rear Panel Isolated Programming & Monitoring connector.
CAUTION:
When the Isolated Analog Option is installed, do not apply any signals to the non-isolated VPGM
and IPGM (J1-6 and J1-5) pins. All other J1 features may be used normally. Refer to Section 4.3.1 for
a description of J1 features.
Parallel operation: Optional Isolated Analog IS510/IS420 must be installed in both the Master and
Slave units.
1
2
3
4
5
6
7
8
Shield
+VPROG_ISO
+IPROG_ISO
GND
Shield
+IMON_ISO
+VMON_ISO
GND
Summary of Contents for Z160-1.3
Page 5: ...This page intentionally left blank...
Page 27: ...26 Pages 26 33 are reserved for Z600 800W...
Page 28: ...27 Pages 26 33 are reserved for Z600 800W...
Page 29: ...34 2 6 Z200W 400W 600W 800W Outline Drawing...
Page 30: ...35 2 7 Z200W 400W 600W 800W Optional IEEE Isolated Analog Interface Outline Drawing...
Page 31: ...36 This Page intentionally left blank...
Page 137: ...NOTES...
Page 138: ...NOTES...
Page 139: ...NOTES...