![TDK-Lambda GXE600 Series Communications Manual Download Page 43](http://html2.mh-extra.com/html/tdk-lambda/gxe600-series/gxe600-series_communications-manual_4197170043.webp)
COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
43/79
#
4
Re gist e r Nam e
Protect Converter
Data Type
Register Function
Starting Address
Qty
Non-volatile
Holding
Configure protection mode
1
Yes
1) Register Details
This is a register that performs GXE operation configuration after exceeding the protection threshold.
GXE can select latch stop and auto recovery as operation when the protection threshold is exceeded.
Select one suitable for system.
Configuration data is retained even when input is cut off.
・Register configuration value
Name
Setting Change
Factory setting
SWOCP
Possible
Auto recovery
HWOCP
Impossible
Latch stop
SWOVP
Possible
Latch stop
HWOVP
Possible
Latch stop
OTP
Impossible
Latch stop
PFCLVP
Impossible
Auto recovery
Reserved
Impossible
-
CNTOFF
Impossible
-
SYSTEM
Impossible
Latch stop
Reserved
Impossible
-
*Write "0" to the bit for which setting change is impossible. Writing '1' is ignored.
Refer the description of the [Protection operation history] register for details on the protection.
・How to set each bit
Select the latch stop and auto recovery by writing the following values to each bit.
Function
Set the protection action when the protection threshold is exceeded to "Auto recovery"
Set the protection action when the protection threshold is exceeded to "Latch stop"
Protection set to "Auto recovery" will release protection after the time set in the "Automatic recovery time" register.
The output of GXE is resumed when the cause of the protection function has been resolved.
Release of the latch stop condition is performed by the following operation.
A. Apply input voltage after input is cut off.
Set at least 3 minutes interval from disconnection to reconnection.
B. Remote on after remote off
The latch is released when GXE output resumes.
0
1
2
102
(0x0066)
Bit
Value
0
1
3
4
5
6, 7
8
9-13
14, 15