COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
25/79
#
2
Re gist e r Nam e
Output Voltage
Data Type
Register Function
Starting Address
Qty
Non-volatile
Input
Monitor value of output voltage
1
No
1) Register Details
This register is measurement value of output voltage. (Between "+ S" and "-S")
Register value is normalized[Q10] signed data with rating.
Data Type
Measurement Range
Accuracy
Normalization [Q10]
0.2 ~ 1.4 [Q10]
+ / - 0.3% of the rating (Ta=25℃)
(Integer notation)
204 ~ 1433
-
※ The value out of measurement range is also returned, but measurement accuracy is not guaranteed.
The actual voltage value is calculated by the following formula.
Output voltage [V] = Nominal Voltage × Register value ( Decimal ) × 2
-10
・GXE output rating
Model
Nominal Voltage
Maximum Current
GXE600-24
24 [V]
25 [A]
GXE600-48
48 [V]
12.5 [A]
Example : When the register reading value is "1000d" in GXE 600-24
Output voltage = 24 × 1000 × 2
-10
= 23.4375 [V]
2) Register Read
R eques t PD U
Read Inputs.
Field
Byte
Value
Function code
1
0x 04
Starting Address
2
1 (0x0001)
Quantity of Registers
2
1 (0x0001)
R es pons e PD U
Read Inputs.
Field
Byte
Value
Function code
1
0x 04
Byte count
1
2 (2 x 1)
Registers value
2
Reading data.
E rror PD U
Read Inputs.
Field
Byte
Value
Function code
1
0x 84
Exception code
1
0x02
1
(0x0001)