COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
39/79
・Terminal input sensitivity
GXE has bounce removal function.
Bounce (chattering) may occur in the signal due to the connection circuit form of the terminal input, but it can be removed
by this function.
The severity of bounce removal can be adjusted with "Terminal input sensitivity".
・Register configuration value
Max
Min
Factory setting
Integer notation
100
0
10
Larger bounces can be removed by increasing the number, but the response to the terminal input will be delayed by
that much.
Changing from the factory setting is unnecessary unless a large mechanical relay or the like is used.
2) Register Read
R eques t PD U
Read Holdings.
Field
Byte
Value
Function code
1
0x 03
Starting Address
2
100 (0x0064)
Quantity of Registers
2
1 (0x0001)
R es pons e PD U
Read Holdings.
Field
Byte
Value
Function code
1
0x 03
Byte count
1
2 (2 x 1)
Registers value
2
Reading data.
E rror PD U
Read Holdings.
Field
Byte
Value
Function code
1
0x 83
Exception code
1
0x02 / 0x04
Data Type
Unit
ms