COMMUNICATION MANUAL
GXE600 SERIES
TDKLambda
<Page>
36/79
#
1
Re gist e r Nam e
Remote On/Off
Data Type
Register Function
Starting Address
Qty
Non-volatile
Holding
Remote On/Off (Volatile)
1
No
Holding
Remote On/Off (Non-Volatile)
1
Yes
1) Register Details
This register manipulates the remote control signal via communication.
It is possible to remotely control the output of the GXE by writing the reference value to the register.
Prior to operation, it is necessary to set "Remote On/Off configuration register" to enable setting of remote control signal
via communication. There are two remote ON / OFF registers, but only the registers set with
"Remote On/Off configuration register" are referenced.
・Register setting value
Value
Function
0
Remote Off
1
Remote On
* If an unspecified value is written, only the lowest bit is accepted as a valid value.
・Remote on / off registers have volatile and nonvolatile registers.
Register
Description
Remote On/Off
GXE will start from the default value each time AC input.
(Volatile)
Because the register value is "Volatile".
Remote On/Off
GXE follows the previously set remote on / off signal.
(Non-Volatile)
Because the register value is "Non-Volatile".
These registers behave differently when brownout occurs for a certain time or more.
The figure below shows the operation image.
The Remote On / Off (Volatile) signal starts from "Remote Off" state even after brownout occurs.
On the other hand, Remote On / Off signal (Non-Volatile) maintains the "Remote On" state even after brownout occurs.
*
Whether " Remote On/Off ( Volatile ) " volatilizes or not depends on the degree of brownout.
- Caution -
The remote control signal is not referred for depending on the setting of "Remote On/Off configuration register".
However, Register value can be changed regardless of whether or not the "Remote On / Off register" is referred.
GXE performs the output operation based on the current register value.
In some cases, output of GXE may be started just by changing the "Remote On/Off configuration register".
Factory setting
AC input
0 : Remote Off
-
(Previously set)
0 : Remote Off
(0x0000)
(0x0001)
0
(0x0000)
5
(0x0005)