Wiring diagram: examples for connecting the relay
Set basic function or standard function at the mode switch
Select the position of the DIP switch 2 according to your system.
When starting or restarting the front-door station, the setting is read out. After starting
the system, the DIP switches 3 and 4 have to be switched to position ON. If not, newly
set values will be overwritten with standard values when restarting the system again.
factory setting
1
not assigned
4
ON
: normal
OFF
: standard address 192.168.1.250, load net settings
3
ON
: normal
OFF
: load parameter factory setting
2
ON
: system peer to peer
direct connection with AVU94x0x
OFF
: system SIP server
Fix the front-door station in the flush-mount box
Fix the front-door station with the included hexagon socket screws through the attache-
ment holes on the studs in the flush-mount box.
Ensure that the screws are not over tightened. The housing of the flush-mount box
could deform and front plate and name plate glass can not be installed resp. removed.