SP60/SP80 User Manual V1.3
TBB Power Co.,Ltd
23
4.4.5 Installing the Battery Temperature Sensor (BTS)
Pull through the BTS cable through gland and connect it on socket marked BTS
Please glue the temperature sensor, which was plugged into BTS socket, on the SIDE of
battery and secure the attachment.
Fig4-4 Glue the temperature sensor
Please notice the cable supplied is around 300cm. Do not pull cable too hard avoid
loose contact loose.
4.4.6 PV array connection
A diode was requested to be added between PV array and SP charge controller
preventing current from battery damage the PV array at night.
The Voc (open circuit voltage) of PV array must never exceed 150Voc. The PV array
Isc must not exceed the nominal current of SP at any time (60A or 80A). Please also
consider the local temperature condition which might result in the increase of PV
array Voc/Isc. Refer to chapter 4.1
Whenever a PV array is exposed to light, a shock hazard exists at the output of wires
or terminals. To reduce the risk, cover the array with a dark material before making
the connection.
Choose the right cable size (refer to 4.3) and follow polarity guide marked on the panel
Adding diode between PV array and MPPT preventing reverse current at night to PV.
An over current protection devices DC fuse or circuit breaker needs to be installed on
positive cable, of which rated for 100% of the nominal rating.
-
SP60-150:
60A