RiiO Sun User Manual

28

internal NTC connection. Contact the
installer if the fault still exists.

6

Transformer NTC fail

7

The battery temperature is too high

Check battery sensor connection;
Check battery temperature; Check
battery connection

8

Abnormal Fan

1.Check whether the fan is blocked.
2.Open the case, check the fan
connection. Contact the installer if the
fault still exists.

14

The system mode and the
parameter setting do not match

Check the parameter setting (Lithium
battery)

16

Abnormal internal communication
of the LCD

Open the case, check the LCD wire
connection. Contact the installer if the
fault still exists.

20

AC input is over voltage

Check the AC input voltage and the
connection

21

AC input is under voltage

22

AC input is over frequency

23

AC input is under frequency

24

Abnormal AC input phase
sequence

30

Abnormal Communication
between the inverter and the DSP

Open the case, check all the inner
connections. Contact the installer if
fault still exists.

31

Software and hardware matching
error

Restart the inverter. Contact installer if
the fault still exists.

6.2.2 MPPT Warning

Warning Code

Description

Solution

62

MPPT current limitation alarm

Check if there is a short circuit at the
output

64

Heat sink NTC fail

Power off the inverter and check the
internal NTC connection. Contact the
installer if the fault still exists.

66

Abnormal Fan

1.Check whether the fan is blocked.
2.Open the case, check the fan
connection. Contact the installer if the
fault still exists.

79

Communication off line

Check the comm connection with the
inverter at the DC Couple system

Summary of Contents for RiiO Sun Series

Page 1: ......

Page 2: ...RiiO Sun User Manual...

Page 3: ...RiiO Sun User Manual WARNING HIGH VOLTAGE INSIDE CAUTION THE DC FUSE MUST HAVE BEENTURNED OFF BEFORE SERVICING MADE IN CHINA...

Page 4: ...in One Solar Inverter This chapter contains important safety and operation instructions Read and keep this User Guide well for later reference The RiiO Sun All in One Solar Inverter needs to be instal...

Page 5: ...1 3 2 Powerful and Reliable Inverter 7 1 3 3 Professional Battery Charger 7 1 3 4 Transfer 9 1 3 5 Protect Function 9 1 3 6 Communication 10 1 3 7 ECO Mode 10 3 Installation and Wiring 11 2 1 Recomme...

Page 6: ...otherwise the RiiO Sun All in One Solar Inverter would be overheating To avoid the fire and the electric shock make sure all cables selected with right gauge and connected well Smaller diameter and br...

Page 7: ...water pump washing machine freezer etc With the function of power assist power control it can be used to work with a limited AC source such as generator or limited grid RiiO Sun can automatically adj...

Page 8: ...ture 2 2 1 Front RiiO Sun 2KVA M RiiO Sun 2KVA S RiiO Sun 3KVA M RiiO Sun 3KVA S RiiO Sun 4KVA S RiiO Sun 3KVA M LV RiiO Sun 3KVA S LV RiiO Sun 5KVA S RiiO Sun 6KVA S Figure 2 1 Front View of the All...

Page 9: ...2 All in One Solar Inverter Control Buttons 2 2 3 Connection compartment RiiO Sun 2KVA M RiiO Sun 2KVA S RiiO Sun 3KVA M RiiO Sun 3KVA S RiiO Sun 4KVA S RiiO Sun 3KVA M LV RiiO Sun 3KVA S LV RiiO Sun...

Page 10: ...t control remote ON OFF control ComMON RS485 port for external monitor such as MCK SNMP Kinergy etc ComSync BMS communication CAN ComSYS System communication RS485 connected to SP or BGK RiiO Sun 2KVA...

Page 11: ...6 2 2 4 Dimension RiiO Sun 2KVA M RiiO Sun 2KVA S RiiO Sun 3KVA M RiiO Sun 3KVA S RiiO Sun 4KVA S RiiO Sun 3KVA M LV RiiO Sun 3KVA S LV RiiO Sun 5KVA S RiiO Sun 6KVA S Figure 2 5 Dimension of the All...

Page 12: ...ensitive equipments computer laser printer TV etc Also your home appliances such as fridge microwave and power tools will work more efficiently High Surge Power Capability Provided with outstanding su...

Page 13: ...in turn can reduce the overall capacity of the battery To improve the life and performance of the flooded battery RiiO Sun provides a manual equalization program that can be used If it is recommended...

Page 14: ...the AC input failure or excessive AC input current set by the user the RiiO Sun All in One Solar Inverter will initiate a quick switching to the inverter which will guarantee an undisturbed power Once...

Page 15: ...th two RS485 interfaces ComSYS System communication RS485 connected to SP or BGK ComMON RS485 port for external monitor such as MCK SNMP Kinergy etc 2 3 7 ECO Mode ECO Mode is to reduce the output pow...

Page 16: ...e temperature 40 70 Cooling Force fan Relative humidity in operation 95 without condensation Altitude 2000m 3 1 Recommended DC cables Please find the following minimum wire size If the DC cable is lon...

Page 17: ...conds to turn on the inverter into the standby mode the power LED will light up and the LCD will enter into the self diagnostic mode Step 3 Wait in the standby mode for 30 seconds then press the On Of...

Page 18: ...play includes four buttons and a LCD display indicating the operating status and input output power information Button Function To exit the setting mode or confirm the fault code To go to the previous...

Page 19: ...lashing Power Assist mode Charge Green Solid on The battery is Charging Flashing The battery is fully Charged Fault Red Solid on Fault occurs Flashing Warning occurs 5 2 LCD Display Icons Icon Functio...

Page 20: ...on to view the warning code Fault flashing every 1 second Press ESC button to view the warning code Output Information Indicates output voltage output frequency load percent load in Watt load in VA an...

Page 21: ...al 16 Indicates the inverter working in a charging mode Indicates the inverter working in a inverting mode Indicates the inverter connecting to the mains or generators Indicates the inverter connectin...

Page 22: ...dification or press the ESC button to cancel The digital tube on the left side of LCD displays PA standing for PASS when the parameters are set successfully otherwise it will display FA standing for F...

Page 23: ...ction and both solar and battery are insufficient to power the load the AC load will be powered by the grid only and the battery will be charged by the grid as well as the solar panel until the batter...

Page 24: ...ower supply to the grid to charge the battery and power the AC load until the battery voltage reaches the set value and the overload is released Then disconnect the grid power supply and restore to th...

Page 25: ...ble Default 0 26 Searchload gate 25 500W Step 1W Default 80W Battery parameter 30 Battery type 0 GEL OPzV 1 AGM 2 Lead Carbon 3 Flooded 4 Traction 5 Customerize 6 TBB SUPER L Only applicable to the co...

Page 26: ...arm voltage 36 Low DC cut off voltage Note Below this voltage the inverter is completely powered down 24V 18 0 22 0V default 19 8V 48V 36 0 44 0V default 39 6V Step 0 1V Low battery protect voltage 37...

Page 27: ...N Default 0 Only in charge mode 47 Battery equalization voltage 24V 31 0 32 6V default 31 0V 48V 62 0 65 2V default 62 0V Step 0 1V Default 15 5V 12V cell 48 Battery equalized time 30 90min Step 5min...

Page 28: ...exceed the limit 0 Disable 1 Enable Default 1 64 Main switch selection In Default state the inverter is controlled through the touch button In Mobile Only mode it is controlled through the rocker swi...

Page 29: ...e time This option is set as Disable by default after the single inverter is powered on again 0 Disable 1 Enable Default 0 75 MPPT Offline alarm control Set whether to display the alarm of disconnecti...

Page 30: ...RiiO Sun User Manual 25 85 Day 0 The last day of this month Default N A 86 Hour 0 23 Default N A 87 Minute 0 59 Default N A...

Page 31: ...inverter Contact the installer in case it still exists 05 The heat sink s temperature is too high Check and assure the inverter has good ventilation 06 The transformer s temperature is too high Too h...

Page 32: ...high Check fan ventilation 24 The heat sink s temperature is too high Too high ambient temperature 25 Abnormal auxiliary power supply Restart the MPPT Contact the installer in case the error still ex...

Page 33: ...ection 21 AC input is under voltage 22 AC input is over frequency 23 AC input is under frequency 24 Abnormal AC input phase sequence 30 Abnormal Communication between the inverter and the DSP Open the...

Page 34: ...e lithium module s charging current is over normal value 46 Fault occurs on the lithium Battery Module 50 The lithium module is over voltage 51 The lithium module is under voltage 52 The lithium modul...

Page 35: ...voltage is lower than the average voltage 83 The single battery voltage is higher than the average voltage 84 The battery temperature is too high 85 NTC fail 86 The Battery Cell voltage does not matc...

Page 36: ...emperature compensation Yes Solar Charger Controller Max output current 60A 40A 60A 90A Maximum PV power 2000W 3000W 4000W 6000W PV open circuit voltage 150V MPPT voltage range 65V 145V MPPT charger m...

Page 37: ...current 60A 60A Maximum PV power 2000W 4000W PV open circuit voltage 150V MPPT voltage range 65V 145V MPPT charger maximum efficiency 98 MPPT efficiency 99 5 Protection a output short circuit b overlo...

Page 38: ...RiiO Sun User Manual 33...

Page 39: ...RiiO Sun User Manual 34...

Page 40: ...RiiO Sun User Manual 35...

Reviews: