RiiO Sun User Manual
19
When the battery type is TBB SUPER-L, the SOC
Ctrl will be displayed, and the ACin First power
supply can be turned on/off according to the
battery SOC.
The SOC value should be set in the TBB LINK
user control interface.
ACin Backup mode:
In the Battery First mode, the AC load will be
powered by the solar power or both solar power
and the battery. When the battery under-voltage
alarm or an overload alarm occurs, the system will
switch its power supply to the grid to charge the
battery and power the AC load until the battery
voltage reaches the set value and the overload is
released. Then disconnect the grid power supply
and restore to the Battery First Mode.
13
Maximum AC in charging current
0~Max(Rate
AC
charge
current)
Step:1A
Default: Max
14
Maximum AC in voltage
240~280V(@230V)
120~140V(@120V)
Step:1V
Default:
265V(@230V)
140V(@120V)
15
Minimum AC in voltage
160~220V(@230V)
80~110V(@120V)
Step:1V
Default:
175V(@230V)
85V(@120V)
16
Maximum AC in frequency
51~55Hz (@50Hz)
61~65Hz (@60Hz)
Step:1Hz
Default:
55Hz (@50Hz)
65Hz (@60Hz)
17
Minimum AC in frequency
42~49Hz (@50Hz)
52~59Hz (@60Hz)
Step:1Hz
Default:
45Hz (@50Hz)
55Hz (@60Hz)
Summary of Contents for RiiO Sun Series
Page 1: ......
Page 2: ...RiiO Sun User Manual...
Page 38: ...RiiO Sun User Manual 33...
Page 39: ...RiiO Sun User Manual 34...
Page 40: ...RiiO Sun User Manual 35...