1-2
TO THE INSTALLER
085592-M
To the Installer
1
Water Connections
Water-Cooled Machines Only:
An adequate cold water
supply must be provided with a hand shutoff valve. On
the underside rear of the base pan, two 3/8 in. I.P.S.
water connections for inlet and outlet have been provided
for easy hookup. Permanently connect machine using
1/2 in. (12.7 mm) inside diameter water lines. (Flexible
lines are recommended, if local codes permit.)
Depending on local water conditions, it may be advisable
to install a water strainer to prevent foreign substances
from clogging the automatic water valve. There will be
only one water-in and one water-out connection.
Do not
install a hand shutoff valve on the water-out line! Water
should always flow in this order: first, through the
automatic water valve; second, through the condenser;
and third, through the outlet fitting to an
open trap drain
.
IMPORTANT!
A backflow prevention device is
required on the incoming water connection side. Please
see the applicable national, state, and local codes for
determining the proper configuration. Water pressure to
the machine must not exceed 150 psi (1034 kPa).
Electrical Connections
Each unit requires one power supply for each data label
on the unit. Check the data label(s) on the freezer for
branch circuit overcurrent protection or fuse, circuit
ampacity, and other electrical specifications. Refer to the
wiring diagram provided inside the electrical box for
proper power connections.
In the United States, this equipment is intended to be
installed in accordance with the National Electrical Code
(NEC) ANSI/NFPA 70-1987. The purpose of the NEC
code is the practical safeguarding of persons and
property from hazards arising from the use of electricity.
This code contains provisions considered necessary for
safety. Compliance therewith and proper maintenance
will result in an installation essentially free from hazard!
In all other areas of the world, equipment should be
installed in accordance with the existing local codes.
Please contact your local authorities.
IMPORTANT!
An equipotential grounding lug is
provided with this machine. Some countries require the
grounding lug be properly attached to the rear of the
frame by the authorized installer. The installation location
is marked by the equipotential bonding symbol (5021 of
IEC 60417-1) on both the removable panel and the
machine's frame.
Electrical Hookup Installation
(60 Cycle, 1 Ph, Supplied with Cord and Plug)
This freezer is supplied with a three-wire cord and
grounding plug for connection to a single-phase, 60-
cycle, branch circuit supply. This unit must be plugged
into a properly grounded receptacle. For example, the
cord and plug provided for 115/60/1 is 20 A; therefore,
the wall outlet must also be 20 A. Check the data label,
located on the side panel, for electrical specifications.
Permanent wiring may be employed if required by local
codes. Instructions for conversion to permanent wiring
are as follows:
•
Be sure the freezer is electrically disconnected.
•
Remove the appropriate panel and locate the
small electrical box at the base of the freezer.
•
Remove the factory-installed cord and strain
relief bushing.
•
Route incoming permanent wiring through 7/8
in. (22 mm) hole in base pan.
•
Connect two power supply leads. Attach ground
(earth) wire to the grounding lug inside the
electrical box.
•
Be sure the unit is properly grounded before
applying power.
Beater Rotation
NOTICE!
Beater rotation must be clockwise as
viewed looking into the freezing cylinder.
!
FOLLOW YOUR LOCAL ELECTRICAL CODES.
Summary of Contents for C152
Page 8: ...1 4 TO THE INSTALLER 085592 M To the Installer 1 Notes ...
Page 36: ...9 2 PARTS REPLACEMENT SCHEDULE 085592 M Parts Replacement Schedule 9 Notes ...
Page 40: ...10 4 LIMITED WARRANTY ON EQUIPMENT 085592 M Limited Warranty on 10 Notes ...
Page 44: ...11 4 LIMITED WARRANTY ON PARTS 085592 M Limited Warranty on Parts 11 Notes ...