9

There are the following operation modes of the fireplace:

Automatic control locked - only manual control of the choke valve is available

Green status diode

blinks.

Setting the choke valve to the rest position ( the

parameter).Green status diode

doesn

t light.

The choke valve is automatically controlled to stabilize temperature of the water

jacket. Green status diode

does light.

Automatic operation is activated by pressing the

ON/OFF

button (3) The choke valve is fully

opened. In 2hrs the fireplace ought to heat itself and reach the preset temperature stabilized by
choke valve movements. From that moment the temperature fall to the preset temperature by
more than 10 C (the

parameter) existing for 30mins is treated as a

burnout of the fireplace. The control unit ends the operation cycle setting the choke valve to the
rest position. Pressing the

ON/OFF

button (3) once more starts another operation cycle.

The green status diode (1) lights during the fireplace operation and goes out after recognizing the
burnout state of the fireplace.

operation icon in waiting for the start of a new cycle (that is, before its start or after

its end

operation icon during the cycle

It

s a stable state, that is, in order to change it you need to press the CHOOSE button.

MAN-

OFF-

ON-

(1)

<50> ChokeV State OFF

(1)

(1)

<23> FPLACE OFF Temp.

AUTO

AUTO

AUTO-

(3)

ON/OFF

.

(1)

0%, full shut-off)

Full automatic burning cycle in the fireplace (firing up - operation - burning out).

Automatic operation is controlled by pressing the button

Green status diode

lights during

the fireplace operation and goes out when the burnt-out state is detected.

At the end of the burning-out phase the choke valve sets to the rest position (

, which

prevents a room from cooling off and protects the water attachment against freezing.

o

Operation screen of the whole system

Temperature

of the water jacket of

the fireplace (T3)

WAW pump

doesn

t run

T2 - temperature

of the WAW container

State of

the CONTROL relay

Operation mode

of the WAW

Time

zone

Current

time

BUF pump runs

PUMPS

T1 - temperature

of the buffer

CH pump

runs

PARAMETERS LEVEL 1

No

NAME

RANGE

SETTING

FUNCTION

20 FIREPLACE

Temp.

45...85

o

C

55

o

C

Preset temperature of the fireplace kept by the control
unit

31

Switch-on Temp.
of PUMPS

30...75

o

C

45

o

C

Minimal temperature of the buffer at which
the CH pump P3 can be activated.

41

Maximum temp.
of WAW

30...99

o

C

60

o

C

Maximal temperature of the WAW container.
The exceeding turns off the loading pump

42

Minimum temp.
of WAW

30...99

o

C

50

o

C

Minimal temperature of WAW container.
The exceeding turns on the loading pump

43 Loading temp.

of WAW special

30...99

o

C

65

o

C

Preset temperature of the fireplace automatically set at
the loading of the WAW

In the priority mode

container.

WAW MODE=SPECIAL

44

Delta Temp.

of WAW

1...10

o

C

2

o

C

Minimal difference between buffer and WAW container

emperature needed for the WAW pump operation P1.

For BUFFER COMBO setup (parameter <93> ) the WAW pump
gets heat from the fireplace and then it

s a minimal temperature

of the fireplace.

t

10

Signal

ON +

ALARM

OFF turns off sound signal
ON turns on sound signal
ON+ALARM turns on sound and alarm

11

Language

Polish/

English/

Deutsch

Polish

DEFAULT

OFF/ON

/ON+

ALARM

PARAMETERS LEVEL 2

No

NAME

RANGE

DEFAULT

SETTING

FUNCTION

70

Zone1 from

0:00...23:4

5

6:00

Start of the 1st time zone

71

Zone1 to

0:00...23:4

5

8:00

End of the 1st time zone

72

0:00...23:4

5

14:00

73

0:00...23:4

5

17:30

74

0:00...23:4

5

20:00

75

0:00...23:4

5

22:30

76

ECO4 from

0:00...23:4

5

23:00

Start of the 4th time zone - economic

77

ECO4 to

0:00...23:4

5

5:00

End of the 4th time zone - economic

78

0:00...23:4

5

8:00

Start of the 5th time zone - economic

79

0:00...23:4

5

13:30

End of the 5th time zone - economic

22

ECO Temp.

-1

-9

o

C

-5

o

C

The lowering of the fireplace temperature in relation to
the preset temperature during the economic time zone

e4

or

e5

13

LCD backlight OFF/ON

OFF

OFF - backlight is active for 2mins from the last pressing
of the button
ON -backlight is active when the control unit
is switched on.
Turning off the backlight means it equals to <15>.next

14

Time zones

OFF/
ON

OFF

OFF-time zones function disabled
ON- time zones enabled acc. to the settings below, that is,
<70>...<79> and <22>

Selection of the language version

Zone2 from

Start of the 2nd time zone

Zone3 from

Start of the 3rd time zone

Zone2 to

End of the 2nd time zone

Zone3 to

End of the 3rd time zone

ECO5 from

ECO5 to

46

PumpWAW-
temp.ON

30...75

o

C

45

o

C

Minimal temperature of the buffer at which the WAW
pump P1 switches on. For BUFFER COMBO setup
(parameter <93> ) the WAW pump gets heat from
the fireplace and then it

s a minimal temperature

of the fireplace.

60

PumpBUF
temp.ON

-

30...75

o

C

48

o

C

Minimal temperature of the fireplace at which
the buffer pump P2 (BUF) can be activated.

15

LCD backlight
minimum

0...25%

10%

Minimal backlight level of the LCD (it

s vital with negative

LCD). The value 0% means a full turn-off

25

WAW in

ECO zone

OFF/ON

ON

ON-WAW loading is switched on in ECO zone
OFF-WAW loading is switched off in ECO zone

Summary of Contents for RT-08G-BUF

Page 1: ...ion conditions 0 50 C humidity 10 90 Housing protection class Fuse 6 3A 250V Number of outputs to control pumps Number of nonvoltage outputs 1 Number of outputs to control the choke valve drive Number...

Page 2: ...temperature of heat source BUFFER for standard configuration FIREPLACE for a configuration with the buffer type COMBO see fig 1 exceeds the value and is higher than the WAW accumulator temperature T2...

Page 3: ...d ISO9001 2000 CERTIFICATE No 133 2004 of 01 2004 Polish Foreign Trade Chamber The last two digits of the year in which the CE marking was affixed 07 Fig 1b Alternative operation diagram of the buffer...

Page 4: ...HE CONTROL UNIT MADE BY A USER CAN BE THE CAUSE OF SAFETY CONDITIONS DETERIORATION AND CAN EXPOSE THE USER TO ELECTRIC SHOCK OR DAMAGE DEVICES SUPPLIED Date of sale Seller s signature and stamp Zak ad...

Page 5: ...is equipped with the CONTROL relay whose contacts can be used e g to switch off another heat source when the fireplace works The parameter definesthefunctionof therelaymoreprecisely see PARAMETERS LEV...

Page 6: ...nged parameter not confirmed for 10 secs is not acceptedby thecontrolunit ON OFF CHOOSE CONFIRM Fig 2 Control panel view 1 Control unit status diode alarm red standby orange operation green manual MAN...

Page 7: ...only at unlocked password To unlock the password you need to input proper sequence of digits with the buttons With the CHOOSE button 7 to change the digits position and CONFIRM button 6 to acknowledge...

Page 8: ...urning off the pumps It prevents from often switchovers especially if there s another heat source in the heating system Buffer limit temperature at which the alarm generates 75 95 o C 85 o C Fireplace...

Page 9: ...he exceeding turns off the loading pump 42 Minimum temp of WAW 30 99 o C 50 o C Minimal temperature of WAW container The exceeding turns on the loading pump 43 Loading temp of WAW special 30 99 o C 65...

Page 10: ...uttons or Pressing theCONFIRM button 6 confirmsthechanges theclockfieldwillstopblinking Normallythe equalsto 0 namelytheparametersaren tavailable After changing the level to 1 2 3 or 4 successive scre...